Table 7.-2
Setting group 2 (Continued)
Variable
Group/
Channel 2
(R, P)
Setting range
Default
setting
Custo-
mer's
setting
Operate time of element
59N-1
2S25
0.10
…
600 s
0.10 s
Resetting time of element
59N-1
2S26
0.07...60.0 s
0.07 s
Pickup value of element
59N-2
2S27
2.0
…
80.0% U
n
(VT)
2.0% U
n
(VT)
Operate time of element
59N-2
2S28
0.10
…
600 s
0.10 s
Predefined time of CBFAIL
2S29
0.10
…
60.0 s
0.10 s
Checksum, SGF1
2S61
0
…
255
0
Checksum, SGF2
2S62
0
…
4095
2730
Checksum, SGF3
2S63
0
…
15
0
Checksum, SGF4
2S64
0...1023
128
Checksum, SGF5
2S65
0
…
255
0
Checksum, SGB1
2S71
0
…
32767
0
Checksum, SGB2
2S72
0
…
32767
0
Checksum, SGB3
2S73
0
…
32767
0
Checksum, SGB4
2S74
0
…
32767
0
Checksum, SGB5
2S75
0
…
32767
0
Checksum, SGR1
2S81
0
…
8191
2730
Checksum, SGR2
2S82
0
…
8191
2730
Checksum, SGR3
2S83
0
…
8191
2730
Checksum, SGR4
2S84
0
…
8191
1365
Checksum, SGR5
2S85
0
…
8191
1365
Checksum, SGR6
S86
0
…
8191
0
Checksum, SGR7
S87
0
…
8191
0
Checksum, SGR8
S88
0
…
8191
0
Checksum, SGL1
S91
0
…
4095
0
Checksum, SGL2
S92
0
…
4095
0
Checksum, SGL3
S93
0
…
4095
0
Checksum, SGL4
S94
0
…
4095
0
Checksum, SGL5
S95
0
…
4095
0
Checksum, SGL6
S96
0
…
4095
0
Checksum, SGL7
S97
0
…
4095
0
Checksum, SGL8
S98
0
…
4095
0
134
REU 610
Voltage Relay
Technical Reference Manual - ANSI Version
1MRS755972
Summary of Contents for REU 610
Page 1: ...Voltage Relay REU 610 Technical Reference Manual ANSI Version ...
Page 2: ......
Page 6: ...6 ...
Page 10: ...10 ...
Page 128: ...128 ...
Page 138: ......
Page 139: ......