Table 5.1.4.7.-10 New trip target timer
Setting
Description
Setting range Default setting
New trip target New trip target timer in minutes
0...998
60
No new trip target allowed until the
previous one has been manually
cleared.
999
-
Non-volatile memory settings
Non-volatile memory is backed up by a battery; the battery must
be inserted and charged.
The table below presents data which can be configured to be stored in the
non-volatile memory. All of the functions mentioned below can be selected
separately with switches 1...5 either via the HMI or the SPA bus.
Table 5.1.4.7.-11 Memory settings
Setting
Switch Function
Default setting
Non-volatile
memory
settings
1
*
0 = operation target messages and
LEDs are cleared
*
1 = operation target messages and
LEDs are retained
1
2
*
1 = disturbance recorder data is
retained
1
3
*
1 = event codes are retained
1
4
*
1 = recorded data and information on
the number of pickups of the protection
elements are retained
1
5
*
1 = the real-time clock is running also
during loss of auxiliary voltage
1
Σ
31
When all switches are set to zero, the battery supervision is
disabled.