59
Function type and information number are mapped into configuration sets
according to the IEC 60870-5-103 standard to the extent that these have been
defined by the standard. If not defined by the standard, the type of function
and/or the information number are/is mapped into a private range.
The tables below indicate the information mapping of the corresponding
configuration sets. The column GI indicates whether the status of the
specified information object is transmitted within the general interrogation
cycle. The relative time in messages with the type identification 2 is
calculated as a time difference between the occurred event and the event
specified in the column Relative time. The measurand multiplied by the
normalize factor is proportional to the rated value. Therefore, the maximum
value of each measurand is the normalize factor multiplied by the rated value.
Table 5.1.14.-1 Information mapping of configuration set 1 and 2
Event reason
Event
code
Configuration
set
1
Configuration
set
2
Function
type
Information
number
GI
Relative
time
Type
identification
Disturbance recorder
Triggered/Cleared
E31/E32
X
X
178
100
-
-
1
HMI password Opened/
Closed
E33/E34
X
X
178
101
-
-
1
59P-1 Pickup/Reset
1E1/1E2
X
X
165
84
X
1E1
2
59P-1 Trip/Reset
1E3/1E4
X
X
165
90
-
1E1
2
59P-2 or 47 Pickup/Reset
1E5/1E6
X
X
165
94
X
1E5
2
59P-2 or 47 Trip/Reset
1E7/1E8
X
X
165
91
-
1E5
2
27P-1 Pickup/Reset
1E9/1E10
X
X
166
84
X
1E9
2
27P-1 Trip/Reset
1E11/1E12
X
X
166
90
-
1E9
2
27P-2 or 27D Pickup/
Reset
1E13/1E14
X
X
166
94
X
1E13
2
27P-2 or 27D Trip/Reset
1E15/1E16
X
X
166
91
-
1E13
2
59N-1 Pickup/Reset
1E17/1E18
X
X
170
84
X
1E17
2
59N-1 Trip/Reset
1E19/1E20
X
X
170
90
-
1E17
2
59N-2 Pickup/Reset
1E21/1E22
X
X
170
94
X
1E21
2
59N-2 Trip/Reset
1E23/1E24
X
X
170
91
-
1E21
2
Trip Lockout/Reset
1E25/1E26
X
X
10
223
X
-
1
External Trip/Reset
1E27/1E28
X
X
10
222
-
-
1
CBFAIL Activated/Reset
1E29/1E30
X
X
160
85
-
-
1
PO1 Activated/Reset
2E1/2E2
X
X
251
27
X
-
1
PO2 Activated/Reset
2E3/2E4
X
X
251
28
X
-
1
1MRS755972
Voltage Relay
Technical Reference Manual - ANSI Version
REU 610
Summary of Contents for REU 610
Page 1: ...Voltage Relay REU 610 Technical Reference Manual ANSI Version ...
Page 2: ......
Page 6: ...6 ...
Page 10: ...10 ...
Page 128: ...128 ...
Page 138: ......
Page 139: ......