77
Table 5.1.16.3.-1 Binary data
Description
DNP point
address
Event class
UR enable
Value range
Comment
Pickup signal from element 59P-1
0
1
1
0/1
1 = activated
Trip signal from element 59P-1
1
1
1
0/1
1 = activated
Pickup signal from element 59P-2
2
1
1
0/1
1 = activated
Trip signal from element 59P-2
3
1
1
0/1
1 = activated
Pickup signal from 27P-1
4
1
1
0/1
1 = activated
Trip signal from element 27P-1
5
1
1
0/1
1 = activated
Pickup signal from element 27P-2
6
1
1
0/1
1 = activated
Trip signal from element 27P-2
7
1
1
0/1
1 = activated
Pickup signal from element 59N-1
8
1
1
0/1
1 = activated
Trip signal from element 59N-1
9
1
1
0/1
1 = activated
Pickup signal from element 59N-2
10
1
1
0/1
1 = activated
Trip signal from element 59N-2
11
1
1
0/1
1 = activated
Trip lockout signal
12
1
1
0/1
1 = activated
External trip signal
13
1
1
0/1
1 = activated
CBFAIL
14
1
1
0/1
1 = failure
PO1
15
1
1
0/1
1 = activated
PO2
16
1
1
0/1
1 = activated
PO3
17
1
1
0/1
1 = activated
SO1
18
1
1
0/1
1 = activated
SO2
19
1
1
0/1
1 = activated
SO3
20
1
1
0/1
1 = activated
SO4
21
1
1
0/1
1 = activated
SO5
22
1
1
0/1
1 = activated
DI1
23
1
1
0/1
1 = activated
DI2
24
1
1
0/1
1 = activated
DI3
25
1
1
0/1
1 = activated
DI4
26
1
1
0/1
1 = activated
DI5
27
1
1
0/1
1 = activated
Disturbance recorder
28
1
1
0/1
1 = triggered
0 = cleared
HMI password
29
1
1
0/1
1 = opened
0 = closed
IRF
30
1
1
0/1
1 = activated
Warning
31
1
1
0/1
1 = activated
SPA event overflow
32
1
1
0/1
1 = activated
1MRS755972
Voltage Relay
Technical Reference Manual - ANSI Version
REU 610
Summary of Contents for REU 610
Page 1: ...Voltage Relay REU 610 Technical Reference Manual ANSI Version ...
Page 2: ......
Page 6: ...6 ...
Page 10: ...10 ...
Page 128: ...128 ...
Page 138: ......
Page 139: ......