Table 5.1.16.3.-2 Analog data
Description
DNP point
address
Event class UR enable
Deadband
Value range
Internal
scaling
factor (ix
= 0)
Phase-to-phase voltage U
ab
0
2
0
1
0...200
100
Phase-to-phase voltage U
bc
1
2
0
1
0...200
100
Phase-to-phase voltage U
ca
2
2
0
1
0...200
100
Residual voltage U
n
3
2
0
1
0...200
100
Positive phase-sequence voltage
4
2
0
1
0...200
100
Negative phase-sequence voltage
5
2
0
1
0...200
100
Table 5.1.16.3.-3 Counters
Description
DNP point
address
Event class UR enable
Deadband Value range
Number of pickups of element 59P-1
0
3
0
1
0...999
Number of pickups of element 59P-2/47
1
3
0
1
0...999
Number of pickups of element 27P-1
2
3
0
1
0...999
Number of pickups of element 27P-2/27D
3
3
0
1
0...999
Number of pickups of element 59N-1
4
3
0
1
0...999
Number of pickups of element 59N-2
5
3
0
1
0...999
Number of trips of element 59P-1 and 59P-2/47
6
3
0
1
0...65535
Number of trips of element 27P-1 and 27P-2/27D
7
3
0
1
0...65535
Number of trips of element 59N-1 and 59N-2
8
3
0
1
0...65535
Number of external trips
9
3
0
1
0...65535
5.1.16.4.
DNP 3.0 device profile of REU 610
DNP V3.00
DEVICE PROFILE DOCUMENT
Vendor Name: ABB Oy, Distribution Automation, Vaasa, Finland
Device Name: REU 610
Highest DNP Level Supported
Device Function
For Requests
L2
Slave
For Responses
L2
Notable objects, functions, and/or qualifiers supported in addition to the Highest DNP
Levels Supported (the complete list is described in the attached table):
Additions to level 2 are marked as shaded in the implementation table
Maximum Data Link Frame Size (octets) Maximum Application Fragment Size
(octets)
Transmitted
292
Transmitted
2048
Received
292
Received
2048
Maximum Data Link Re-tries:
Maximum Application Layer Re-tries: