Sometimes (attach explanation)
ENABLE/DISABLE UNSOLICITED
Function codes supported
No other options are permitted.
Default Counter Object/Variation
Counters Roll Over at
No Counters Reported
No Counters Reported
Configurable, default object and
variation
Configurable (attach explanation)
Default Object 20
Default Variation 2
16 Bits (Counters 6...9)
Point-by-point list attached
32 Bits, but roll-over bits not used
Other value: 999 (Counters 0...5) and
255 (Counters 10...21)
Point-by-point list attached
Sends Multi-Fragment Responses
Yes
No
Table 5.1.16.4.-1 Supported function codes
Code
Function
Description
Supported
Transfer Function Codes
0
Confirm
Message fragment confirmation
No response
Yes
1
Read
Request objects from outstation
Respond with requested objects
Yes
2
Write
Store specified objects to outstation
Respond with status of operation
Yes
Control Function Codes
3
Select
Select output point of outstation
Respond with status of control point
No
4
Operate
Set previously selected output
Respond with status of control point
No
5
Direct operate
Set output directly
Respond with status of control point
No
6
Direct operate NO ACK
Set output directly
No response
No
Freeze Function Codes
7
Immediate Freeze
Copy specified objects to freeze buffer
Respond with status of operation
Yes
8
Immediate Freeze NO ACK
Copy specified objects to freeze buffer
No response
Yes
9
Freeze and Clear
Copy specified objects to freeze buffer and clear
objects
Respond with status of operation
Yes
a)
10
Freeze and Clear NO ACK
Copy specified objects to freeze buffer and clear
objects
No response
Yes
a)
11
Freeze with time
Copy specified objects to freeze buffer at specified time
Respond with status of operation
No