Table footnotes from previous page
a)
0 = rising edge; 1 = falling edge.
Table 5.1.17.-6 Disturbance recorder external triggering and storing
Event
Weighting
factor
Default value
of triggering
mask, V241
Default value
of triggering
edge, V242
a)
Default value
of storing
mask, V243
DI1
1
0
0
0
DI2
2
0
0
0
DI3
4
0
0
0
DI4
8
0
0
0
DI5
16
0
0
0
Σ
0
0
0
a)
0 = rising edge; 1 = falling edge.
Control parameters
Table 5.1.17.-7 Control parameters
Description
Parameter
R, W, P
Value
Reading of the event buffer
L
R
Time, channel number and event code
Re-reading of the event buffer
B
R
Time, channel number and event code
Reading of relay state data
C
R
0 = Normal state
1 = The relay has been subject to an
automatic reset
2 = Overflow of the event buffer
3 = Both 1 and 2
Resetting of relay state data
C
W
0 = Reset E50 and E51
1 = Reset only E50
2 = Reset only E51
4 = Reset all events including E51 except
for E50
Time reading and setting
T
R, W
SS.sss
Date and time reading and setting
D
R, W
YY-MM-DD HH.MM;SS.sss
Type designation of the relay
F
R
REU 610
Unlatching output contacts
V101
W
1 = Unlatch
Clearing targets and memorized values and
unlatching contacts (master reset)
V102
W
1 = Clear and unlatch
Resetting of trip lockout
V103
W
1 = Reset
Rated frequency
V104
R, W (P)
50 or 60 Hz
Time setting range for demand values in
minutes
V105
R, W
0...999 min
Non-volatile memory settings
V106
R, W
0...31
Time setting for disabling new trip targets on
the LCD
V108
R, W (P)
0...999 min
96
REU 610
Voltage Relay
Technical Reference Manual - ANSI Version
1MRS755972
Summary of Contents for REU 610