![background image](http://html1.mh-extra.com/html/abb/reu615/reu615_manual_3437524026.webp)
2.3.5.3
LD0.VMMXU1 Three-phase voltage limit supervision
Table 18:
LD0.VMMXU1 Three-phase voltage limit supervision
IEC 61850 name
SA name
Description
Values
LD0.VMMXU1
.HiAlm.stVal
HIGH_ALARM
High alarm
1=Alarm
.HiWrn.stVal
HIGH_WARN
High warning
1=Warning
.LoAlm.stVal
LOW_ALARM
Low alarm
1=Alarm
.LoWrn.stVal
LOW_WARN
Low warning
1=Warning
2.3.5.4
LD0.RESVMMXU1 Residual voltage limit supervision
Table 19:
LD0.RESVMMXU1 Residual voltage limit supervision
IEC 61850 name
SA name
Description
Values
LD0.RESVMMXU1
.HiAlm.stVal
HIGH_ALARM
High alarm
1=Alarm
.HiWrn.stVal
HIGH_WARN
High warning
1=Warning
2.3.6
Protection functions
2.3.6.1
LD0.LEDPTRC1 Global protection signals
Table 20:
LD0.LEDPTRC1 Global protection signals
IEC 61850 name
SA name
Description
Values
LD0.LEDPTRC1
Global protection signals
.Op.general
-
-General Operate
1=Operate
.Op.phsA
-
-phsA Operate
1=Operate
.Op.phsB
-
-phsB Operate
1=Operate
.Op.phsC
-
-phsC Operate
1=Operate
.Str.general
-
-General Start
1=Start
.Str.phsA
-
-phsA Start
1=Start
.Str.phsB
-
-phsB Start
1=Start
.Str.phsC
-
-phsC Start
1=Start
2.3.6.2
LD0.TRPPTRC1 Global conditioning (1)
Table 21:
LD0.TRPPTRC1 Global conditioning (1)
IEC 61850 name
SA name
Description
Values
LD0.TRPPTRC1
.Op.general
-
Operate input signal
1=Operate
.Tr.general
-
Trip output signal
1=Trip
Section 2
1MRS757056 C
DNP3 data mappings
20
REU615
Point List Manual