112
1MRS751802-MUM
Protection Relay
Technical Reference Manual, Standard Configurations
REX 521
7.2.2.
I<->O IND1 and I<->O IND2
The object indication function blocks I<->O IND1 and I<->O IND2 indicate the
open, close and undefined states of a disconnector or an earthing switch.
7.2.3.
I<->O POS
The function block for logic control position selector, I<->O POS, makes it possible
to choose remote or local position via the input Remote, which facilitates the flexible
selection of control position. The Remote input can be found in
Main
menu\Configuration\Input Signals\Remote
.
In remote position, the circuit breaker can only be controlled via remote
communication and, accordingly, the local position only enables operation via the
HMI and the digital inputs.
Fig. 7.2.3.-1
Function block symbol of I<->O POS
7.2.4.
I<->O IND3
The object indication function block I<->O IND3 indicates the state of the motor
(running/stopped) in H07.
7.2.5.
ALARM1-8
The alarm indicating functions ALARM1-8 are used for controlling alarm LEDs.
The configuration-specific signals to which the alarm indicating functions can be
connected are the following:
I<->O POS
BINREMOTE
Table 7.2.5-1
Basic B01
LED1
LED2
LED3
LED4
LED5
LED6
LED7
LED8
3I> Start
3I> Trip
3I>> Start
3I>> Trip
3I>>> Start
3I>>> Trip
Io> Start
Io> Trip
Io>> Start
Io>> Trip
Io>>> Start
Io>>> Trip
Iub> Start
Iub> Trip
3Ith> Start
3Ith> Trip
DI1
DI2
DI3
DI4
DI5
DI6
DI7
DI8
DI1
DI2
DI3
DI4
DI5
DI6
DI7
DI8
MEAS HI ALARM
DI2
DI3
DI4
DI5
DI6
DI7
Interlocking
MEAS LO ALARM
MEAS HI ALARM
DI3
DI4
DI5
DI6
DI7
Lockout
CB Wear
TCS1
MCS 3I
DI4
DI5
DI6
DI7
DI8
Table 7.2.5-2
Basic B02
LED1
LED2
LED3
LED4
LED5
LED6
LED7
LED8
3I> Start
3I> Trip
3I>> Start
3I>> Trip
3I>>> Start
3I>>> Trip
Io> Start
Io> Trip
Io>> Start
Io>> Trip
Io>>> Start
Io>>> Trip
Iub> Start
Iub> Trip
3Ith> Start
3Ith> Trip
O->I OPEN
O->I ACTIVE
O->I ALAR1
O->I ALAR2
DI1
DI2
DI3
DI4
DI5
DI6
DI7
DI8
DI1
DI2
DI3
DI4
DI5
DI6
DI7
DI8
MEAS HI ALARM
DI2
DI3
DI4
DI5
DI6
DI7
Interlocking
MEAS LO ALARM
MEAS HI ALARM
DI3
DI4
DI5
DI6
DI7
Lockout
CB Wear
TCS1
MCS 3I
DI4
DI5
DI6
DI7
DI8
Summary of Contents for REX 521
Page 1: ...Protection Relay REX 521 Technical Reference Manual Standard Configurations ...
Page 2: ......
Page 12: ...12 ...
Page 22: ...22 ...
Page 62: ...62 ...
Page 72: ...72 ...
Page 128: ...128 ...
Page 132: ...132 ...
Page 172: ...172 ...
Page 198: ...198 ...
Page 249: ......