1MRS751802-MUM
REX 521
117
Protection Relay
Technical Reference Manual, Standard Configurations
Recording can be triggered on the rising or falling edge of any or several of the
digital inputs, on an adjustable level of overcurrent, overvoltage or undervoltage, or
the recording can be triggered manually via the HMI, via serial communication or a
parameter, or using a periodic triggering.
Notice that the recordings will be cleared if setting some of the parameters which
cause the device to reset.
Refer to Technical Reference Manual, General, chapter "Relay Setting Tool view"
(see Section 1.5. Related documents).
Fig. 7.3.4.-1
Function block symbol of DREC
DREC
IL1
IL2
IL3
Io
Iob
BI1
BI2
BI3
BI4
BI5
BI6
BI7
BI8
BI9
BI10
BI11
BI12
BI13
BI14
BI15
BI16
EXT_TRG
Start 3I>
Start 3I>>
Start 3I>>>
Start Io>
Start Io>>
Start Io>>>
Start 3Iub>
Start 3Ith>
Trip 3I>
Trip 3I>>
Trip 3I>>>
Trip Io>
Trip Io>>
Trip Io>>>
Trip 3Iub>
Trip 3Ith>