1MRS751802-MUM
REX 521
143
Protection Relay
Technical Reference Manual, Standard Configurations
9.1.5.1.
Outgoing blocking signal to the incoming feeder
The start signals from any protection function can be routed to an output relay to
provide a blocking signal to the incoming feeder. The overcurrent stages 3I>> and
3I>>> have also a separate BSOUT signal for blocking purpose.
To use the start signal from a protection function the signal has to be routed via the
Main menu\Configuration\Output SWGRP\Start 1
or
\Start 2
. When the start signals have been routed, the output relay has to be
selected in the
Main menu\Configuration\Output Signals
. In this
example, the overcurrent stage 3I>> is routed via Start 1 and then connected to the
power output 2, PO2. In this application example, the checksum for the Start 1 is 2.
9.1.5.2.
Blocking signal received from the residual voltage relay
To release blocking, the start signals from a residual voltage relay can be connected
to the earth fault stages in the outgoing feeder. There are two input blocking signals,
Blocking 1 and Blocking 2, which can have different functions depending on the
different protections.
The Blocking 1 input signal is connected to the BS1 input and the Blocking 2 input
signal is connected to the BS2 input of the earth fault-stages Io>, Io>> and Io>>>.
The BS1 in this application example will stop the DT (Definite time) or the IDTM
(Inverse Definite Time) timer and the BS2 will block the trip signal. Refer to the CD-
ROM
Technical Descriptions of Functions
(see Section 1.5. Related documents) for
more information.
In this application example, the digital input DI9 is connected to the input signal
Blocking 1 and then routed to the BS1 input of the earth fault stage Io>. The
Blocking 1 signal can be found in
Main menu\Configuration\Input
Signals\Blocking 1\
where the DI9 is selected. The checksum for the
switchgroup in
Main menu\Configuration\Input SWGRP\
Blocking 1\
is 8 to block Io>.
Normally the Blocking 1 signal is set to release the Io> blocking when the residual
voltage relay starts, and give the Io> protection a permission to start and further
execute trip after the set time delay has elapsed. For instance, this can be established
by inverting the digital input DI9 and use the start signal from the residual relay for
permission.
9.1.5.3.
Circuit-breaker failure protection
Every protection function in the standard configuration B01 provides a delayed trip
signal CBFP after the trip signal unless the fault has not disappeared during the set
CBFP time delay. In circuit-breaker failure protection, the CBFP output can be used
for operating an upstream circuit-breaker.
The settings for the breaker failure are set separately for each protection function.
For example, to set the CBFP time for the 3I>> go to
Main menu\Protection\3I>>\Control settings
, where it is possible
to set the
CBFP time
from 100 ms to 1000 ms. The control parameter
Trip
pulse
sets the width of the trip output signal, but also of the CBFP output signal.
Summary of Contents for REX 521
Page 1: ...Protection Relay REX 521 Technical Reference Manual Standard Configurations ...
Page 2: ......
Page 12: ...12 ...
Page 22: ...22 ...
Page 62: ...62 ...
Page 72: ...72 ...
Page 128: ...128 ...
Page 132: ...132 ...
Page 172: ...172 ...
Page 198: ...198 ...
Page 249: ......