All of the protection functions in the standard configuration M01 provide a delayed
trip signal CBFP after the trip signal unless the fault has not disappeared during the
set CBFP time delay. In the circuit-breaker failure protection, the CBFP output can
be used for operating an upstream circuit breaker.
The settings for breaker failure are set separately for each protection function. For
example, to set the CBFP time for 3I>> go to
Main menu\Protection\3I>>\Control setting
where it is possible to
set the
CBFP time
from 100 ms to 1000 ms. The control parameter
Trip pulse
sets the width of the trip output signal, but also of the CBFP output signal.
The CBFP signals from the protection functions are routed to the output signals via
the output switchgroups. These settings can be found in
Main menu\Configuration\Output SWGRP\CBFP
. When the two-stage
overcurrent, the two-stage directional earth fault, the unbalance and thermal
overload protection are selected, the checksum for CBFP will be 221.
The CBFP signal is then connected to any of the output relays via
Main menu\Configuration\Output Signals\
, and in this example the
circuit-breaker failure signal is connected to the power output 1, PO1.
10.2.5.7.
Trip-circuit supervision
The trip-circuit supervision is available for the HSPO1 relay. If the resistance of the
trip circuit exceeds a certain limit, for instance due to a bad contact or oxidation, the
supervision function will be activated and a trip-circuit supervision alarm signal will
be provided after an adjustable delay time. The settings for the function can be found
in
Main menu\Cond. monit.\TCS1\
.
To avoid unnecessary alarms the trip-circuit supervision can be blocked by the BS
signal, which disables the supervision output when the circuit breaker is open. The
BS signal is configured to be operated by the “CB pos. open” status from the selected
digital input. The BS signal can be connected via the switchgroup in
Main menu\Input SWGRP\TCS1\
. The default setting of the parameter is
”Not in use”.
Another solution is to use an external resistor to prevent the TCS1 alarm. Refer to
REX 521 Technical Reference Manual, General
documents) for more information about the trip-circuit supervision.
Summary of Contents for REX 521
Page 1: ...Protection Relay REX 521 Technical Reference Manual Standard Configurations ...
Page 2: ......
Page 12: ...12 ...
Page 22: ...22 ...
Page 62: ...62 ...
Page 72: ...72 ...
Page 128: ...128 ...
Page 132: ...132 ...
Page 172: ...172 ...
Page 198: ...198 ...
Page 249: ......