11. Application
examples,
High
11.1.
Incoming feeder, High H01
11.1.1.
Features
This application example describes an incoming feeder to a single busbar with
parallel feeders including:
• Directional overcurrent protection
• Non-directional overcurrent protection
• Synchro-check and voltage-check
This application example is an optional solution for the application example 9 (see
Section 11.2. Incoming feeder, High H02), if there is a parallel generator feeder
connected to the same busbar.
The network is either compensated earthed or isolated. The directional overcurrent
protection is used because of the parallel feeders. There is no earth fault protection
included in this application example, because residual voltage-based protection can
be located on the measurement cubicle of the busbar.
The three-phase current measurement is established with Rogowski sensors and the
residual voltage is calculated from phase-to-earth voltages which are measured by
the voltage dividers. Phase-to-phase voltage of the busbar for synchro- and voltage-
check is measured by the voltage transformer.
Fig. 11.1.1.-1
REX 521 High H01 used for protection, measuring and supervision
on an incoming feeder in a single busbar system with parallel
generator feeder. The system earthing on the supplying network is
compensated or isolated.
REX 521 H01
Application Example 8
3I>
67
f
P
3U
3I
Q
E
pf
TCS
CBCM
0
I
MCS
3I~harm
000
R
CBFP */62
U
0
3I >
50/51
SYNC
25
VD
G
User
IncH01
Summary of Contents for REX 521
Page 1: ...Protection Relay REX 521 Technical Reference Manual Standard Configurations ...
Page 2: ......
Page 12: ...12 ...
Page 22: ...22 ...
Page 62: ...62 ...
Page 72: ...72 ...
Page 128: ...128 ...
Page 132: ...132 ...
Page 172: ...172 ...
Page 198: ...198 ...
Page 249: ......