74
1MRS751802-MUM
Protection Relay
Technical Reference Manual, Standard Configurations
REX 521
5.1.5.
Power quality trigger
Any of the inputs DI1...DI9 can be used to start the power quality recording
measurements.
5.1.6.
Master trip
An external trip signal can be routed to the heavy duty tripping contact via
DI1...DI9. (The Master trip function bypasses the interlocking sequence.)
Master trip can be utilized by using the input selector Master trip to connect one of
the digital inputs (DI1...DI9) to the high speed tripping relay (HSPO1).
5.1.7.
External trip
An additional external trip signal can be routed to the output relays PO1...PO3 and
SO1...SO2 (The external trip function bypasses the blocking sequence).
5.1.8.
Lockout reset
Any DI1...DI9 can be programmed to reset the Lockout function.
5.1.9.
Local/Remote
Any of the digital inputs can be used for activating the local mode of the relay if the
Local/Remote selection is set to “external input”. In local position, the circuit
breaker can be controlled via the binary inputs and the HMI but not through a
communication port. In remote position, the circuit breaker can be controlled only
through a communication port.
5.1.10.
Close enable
DI1...DI9 can be used for giving the permission to close the circuit breaker. For
example, SF6 gas low indication signal can be used to block the close operation of
the CB (The Close command can be activated either via the digital inputs, the HMI
or through the communication port).
5.1.11.
Direct control (Open/Close)
DI...DI9 can be used for controlling the circuit breaker.
When using digital inputs to control the circuit breaker, the inputs must
be activated with a pulse. Otherwise, if the input remains activated, a
position change from remote to local can cause an immediate opening or
closing of the circuit breaker.
5.1.12.
Object indication
Object indication is used to collect object status indications to MicroSCADA. The
interlocking logic also uses the logical states of the digital inputs (according to the
selected interlocking option).
The transferring of object status indication data to MicroSCADA is achieved by
using the I<->O IND1 and I<->O IND2 function blocks.
!
Summary of Contents for REX 521
Page 1: ...Protection Relay REX 521 Technical Reference Manual Standard Configurations ...
Page 2: ......
Page 12: ...12 ...
Page 22: ...22 ...
Page 62: ...62 ...
Page 72: ...72 ...
Page 128: ...128 ...
Page 132: ...132 ...
Page 172: ...172 ...
Page 198: ...198 ...
Page 249: ......