1MRS751802-MUM
REX 521
119
Protection Relay
Technical Reference Manual, Standard Configurations
DREC digital inputs:
(Trip 1, Trip 2, and Trip 3 are the Output SWGRP signals.)
1
H01 not available with transformers.
2
H08/H09 not available with sensors.
7.3.5.
3U
The measurement function block 3U measures true RMS phase-to-earth or phase-to-
phase voltages. If voltage dividers are used, as in configurations H01S-H07S, only
phase-to-earth voltages can be measured. If voltage transformers are used, as in
configurations H02-H07, only phase-to-phase voltages can be measured. As an
exception from these, in configuration H08, voltage transformers are used and
phase-to-earth voltage is measured. The voltage values are updated once per
fundamental frequency cycle, that is, the integration time for true RMS calculation
is one fundamental cycle.
Fig. 7.3.5.-1
Function block symbol of 3U
Input B01/B02 M01/M02
H01
1
H02
H03
H04
H05/H08
2
H06
H07
H09
2
BI1
Start 3I>
Start 3I>
Start 3I>->
Start 3I>->
Start 3I>
Start 3I>
Start 3I>
Start 3I>
Start 3I>
Start 3I>
BI2
Start 3I>>
Start 3I>>
Start 3I>>->
Start 3I>>->
Start 3I>>
Start 3I>>
Start 3I>>
Start 3I>>
Start 3I>>
Start 3I>>
BI3
Start 3I>>> Start 3I>>>
Start 3I>>>
Start 3I>
Start 3I>>>
Start 3I>>>
Start 3I>>>
Start 3U>
Start 3I>>>
Start 3I>>>
BI4
Start Io>
Start Io>->
Start Io>->
Start 3I>>
Start Io>->
Start Io>->
Start Io>
Start 3U>>
Start Io>->
Start Io>
BI5
Start Io>>
Start Io>>->
Start Io>>->
Start Io>->
Start Io>>->
Start Io>>->
Start Io>>
Start 3U<
Start Io>>->
Start Io>>
BI6
Start Io>>> Start Io>>>-> Start Io>>>-> Start Io>>-> Start Io>>>-> Start Io>>>-> Start Io>>>
Start 3U<<
Start Io>
Start Io>>>
BI7
Start Iub>
Start Iub>
Start Iub>
Start Io>>>-> Start Iub>
Start Io>
Start 3U>
Start Uo>
Start Io>>
Start 3U>
BI8
Start 3Ith> Start 3Ith>
Start 3Ith>
Start Iub>
Start 3Ith>
Start Io>>
Start 3U>>
Start Uo>>
Start 3Ithdev>
Start 3U>>
BI9
Trip 3I>
Trip 3I>
Trip 3I>->
Start 3Ith>
Trip 3I>
Start Io>>>
Start 3U<
Start Uo>>>
Start I2>/I2>>
Start 3U<
BI10
Trip 3I>>
Trip 3I>>
Trip 3I>>->
Start1 f1
Trip 3I>>
Start Iub>
Start 3U<<
Start 1 f1
Start Is2t n<
Start 3U<<
BI11
Trip 3I>>>
Trip 3I>>>
Trip 3I>>>
Start2 f1
Trip 3I>>>
Start 3Ith>
Start Uo>
Start 2 f1
Start 3I<
Start Uo>
BI12
Trip Io>
Trip Io>->
Trip Io>->
Trip1
Trip Io>->
Start 3I>->
Start Uo>>
Start 1 f2
Start 3U>/3U>> Start Uo>>
BI13
Trip Io>>
Trip Io>>->
Trip Io>>->
Trip2
Trip Io>>->
Start1 f1
Start Uo>>>
Start 2 f2
Start 3U</3U<< Start Uo>>>
BI14
Trip Io>>> Trip Io>>>->
Trip Io>>>->
Trip3
Trip Io>>>->
Start2 f1
Trip 1
Trip 1
Start1/Start2 f1 Start1/Start2 f1
BI15
Trip Iub>
Trip Iub>
Trip Iub>
-
Trip Iub>
Trip1
Trip 2
Trip 2
Trip1
Start1/Start2 f2
BI16
Trip 3Ith>
Trip 3Ith>
Trip 3Ith>
-
Trip 3Ith>
Trip2
Trip 3
Trip 3
Trip2
Trip1
3U
UL1_U12
UL2_U23
UL3_U31
MEVO3A
Summary of Contents for REX 521
Page 1: ...Protection Relay REX 521 Technical Reference Manual Standard Configurations ...
Page 2: ......
Page 12: ...12 ...
Page 22: ...22 ...
Page 62: ...62 ...
Page 72: ...72 ...
Page 128: ...128 ...
Page 132: ...132 ...
Page 172: ...172 ...
Page 198: ...198 ...
Page 249: ......