Compact current relay and
protection assemblies
RXHL 401 and
RAHL 401
1MRK 509 062-BEN
Page 11
Table 2: Binary inputs
Table 3: Output relays
Table 4: Auxiliary DC voltage supply
Table 5: Electromagnetic compatibility (EMC), immunity test
Inputs
Rated values
Binary inputs
2
Binary input voltage RL
48-60 V DC and 110-220 V DC, -20% to +10%
Power consumption
48-60 V DC
< 0.3 W / input
110-220 V DC
< 1.0 W / input
Outputs
Rated values
Contacts
5 change-over
Maximum system voltage
250 V AC/DC
Current carrying capacity
Continuous
5 A
During 1 s
15 A
Making capacity at inductive
load with L/R >10 ms
During 200 ms
30 A
During 1 s
10 A
Breaking
capacity
AC, cos
ϕ
> 0.4
max. 250 V
8 A
DC, L/R < 40 ms
48 V
1 A
110 V
0.4 A
220 V
0.2 A
250 V
0.15 A
Power consumption
Rated values
Auxiliary voltage EL for RXTUG 22H
24-250 V DC, +/-20%
Auxiliary voltage for the relay
+/-24 V (from RXTUG 22H)
Power consumption
with back-light on
With RXTUG 22H,
input 24-250 V
Before operation
< 5.0 W
After operation
< 7.0 W
Without RXTUG
22H, +/-24 V
Before operation
< 2.7 W
After operation
< 4.3 W
Power consumption, back-light.
Approximately 0.5 W
All tests are performed together with the DC/DC-converter, RXTUG 22H
Test
Severity
Standard
Surge
1 and 2 kV
IEC 61000-4-5, class 3
AC injection
500 V AC
SS 436 15 03, PL 4
Power frequency magnetic field
1000 A/m
IEC 61000-4-8