ABB | SACE Emax 2
Ekip Touch protection release | 14 - Touch measurements
125 | © 2013
ABB |
1SDH001000R0002 - L7804
Events
Path
Main page - Menus - Measurements - History
Description
The release can record the last 200 events, referring mainly to variations in status and operation.
Specifically, the recorded events can supply information on:
• Release: configuration status of the bus, operating mode, active set, auxiliary power supply.
• Protections: delay in action or alarm.
• Connection states or alarms: circuit-breaker, current sensors, trip coil, rating plug.
• Tripping: status of the opening command, or signal of opening for protection.
NOTE:
in the list of the events, the first available is the most recent one. If the release
has exceeded the threshold of 200 events, the oldest ones are progressively overwritten.
Correlated information
Every event is correlated by the following information:
• Icon that identifies the type.
• Name
• Date and time.
There are 4 icons that identify the type of event:
Icon
Description
Event reported for information purposes.
Delay of a protection in progress, trip expected.
Alarm referring to a non-hazardous condition.
Alarm for operation, failure, or connection fault.