ABB | SACE Emax 2
Ekip Touch protection release | 17 - Test
143 | © 2013
ABB |
1SDH001000R0002 - L7804
Continued from the previous page
RC test
Submenus for the test of the Rc sensor involve the command
Self-test.
that allows the
command to be sent to the RC sensor to check on the correct operation.
NOTE:
the test is available only with sensor correctly connected, release in Rc
configuration, auxiliary power supply present.
Protection test
To perform the protection command test, follow the following procedure:
Phase
Operation
1
Make sure that the circuit-breaker is closed and that there are no currents
circulating
2
Connect a test front unit between Ekip T&P or Ekip Bluetooth
3
Start the communication with Ekip Connect
4
Open the Information page and select the Test command, which opens the
protection test page
5
Set up the test as required and verify that the release functions properly