ABB | SACE Emax 2
146 | © 2013
ABB |
1SDH001000R0002 - L7804
Ekip Touch protection release | 18 - Self-diagnosis
Programming errors
If during the programming of the parameters an attempt is made to violate certain limitations,
the release blocks the saving procedure and signals the error:
Type of error
Error description
L Th
≥
S Th
Errors in the adjustment of the protection
thresholds
S Th
≥
I Th
Errors in the adjustment of the protection
thresholds
L Th
≥
S2 Th
Errors in the adjustment of the protection
thresholds
S2 Th
≥
I Th
Errors in the adjustment of the protection
thresholds
L Th
≥
D Th
Errors in the adjustment of the protection
thresholds
D Th
≥
I Th
Errors in the adjustment of the protection
thresholds
D Zone Sel = On while S / S2/ G / Rc = On
Activation of zone selectivity with
protections S, S2, G or Rc enabled
S(V) t20 and S(V) I20 error
Incorrect configuration of the protection S(V)
RQ Q24 > Q25
Incorrect configuration of the protection RQ
SYNCHRO parameters error
Error in the parameters of the Ekip
Synchrocheck module
ROCOF t28 error
Incorrect configuration of the protection
ROCOF
And the MCR enabled together
Simultaneous enabling of the protections I
and MCR
High priority alarm
Protection and delay alarms present during
programming
Rc toroid error
An attempt is made to activate the RC
sensor without Ekip Measuring or RC type
rating plug
Internal neutral config error
It tries to set the internal neutral setting with
a value that is not allowed
Change nr datalogger with dlogger not
stopped
Change datalogger parameters with
datalogger active
Reverse pole order error
Change in the parameter "pole order" with a
Half size circuit-breaker.
Programming Session Timeout
Timeout for saving data