ABB | SACE Emax 2
Ekip Touch protection release | 21 - Ekip Power Controller
151 | © 2013
ABB |
1SDH001000R0002 - L7804
21 - Ekip Power Controller
Characteristics
Presentation
The Ekip Power Controller function allows you to manage the load of an installation according
to the power input, in order to contain the consumptions and to optimize the energy efficiency.
The configuration of the various parameters related to the this functionality is available through
a dedicated tool inside the Ekip Connect software.
All the detailed information on the Power Controller function is provided in
White Paper
1SDC007410G0901.
Releases
The functionality Ekip Power Controller can be activated for all the releases of the Ekip TOUCH
range, and allows you to do the following via display:
• Modify some of the parameters of the function.
• Display some measurements of the function.
• View the status of the loads.
NOTE:
the Ekip Power Controller function is available if requested when ordering the
CB or the protection Release.
Parameters on the display
The parameters available following the path
Main page - Menus - Settings - Power Controller
are:
Parameter
Description
Enable
It allows you to activate/deactivate the Ekip Power Controller
function.
Load Operating
Mode
It allows you to set the configuration of each of the 15
programmable loads
Automatic or Manual configurations available.
Power limits
It allows you to set the 4 power limits (from 0 to 5000 kW, step
5kW).
NOTE:
for the characterization of all the parameters of the function you are advised
to configure the parameters via Ekip Connect first, and only subsequently to operate
on the release in order to enable or to modify load and power limits.
Continued on the next page