ABB | SACE Emax 2
188 | © 2013
ABB |
1SDH001000R0002 - L7804
Electronic accessories | 5 - Ekip Signalling 2K modules
Continued from the previous page
The following table illustrates configuration parameters of the outputs:
Parameter
Selectable values
Default
Description
Signal
source
• None
• Prealarm L
• Delay L
• Delay S
• Opening L
• Opening S
• Opening G
• Opening I
• Every opening
• Every alarm
• Load LC1
(1)
• Load LC2
(1)
• CB Open
• CB Close
• Custom
(2)
None
The event that the output must activate,
that is, with which the contact must be:
• Closed, if set as NO.
• Open, if set as NC.
Delay
00…100.00 s
in steps of 0.01 s
0.00 s
Standby time after the selected event
has taken place, and before the output is
activated (if the event disappears before
a time equal to the delay has passed,
the output is not activated). If 0.00 s is
selected, the value 300
μ
s is assigned to
the parameter.
Contact
Type
NO, NC
NO
• NO = Contact normally open.
• NC = Contact normally closed.
Self-latching Off, On
Off
• Off = The output is deactivated when
the event disappears.
• On = When the event disappears, the
output is kept active for the minimum time
selected.
IMPORTANT: if the output is used
for the Power Controller function,
self-latching must not be enabled.
min
Activation
Time
0 ms, 100 ms,
200 ms, Power
Controller
0 ms
The "Power Controller" value must be
selected if the output is used for the Power
Controller function (see the chapter "21 -
Ekip Power Controller", on page 151). The
output is then kept active for a fixed time
dictated by the function, independently of
the persistence of the event that activated
it.
On the contrary, with self-latching enabled,
the minimum time in which the output is
kept active (once the selected time has
elapsed, the output is kept active as long
as the event that activated it persists).
IMPORTANT: if the output is not
used for the Power Controller
function, the “Power Controller”
value must not be selected.
(1)
For the sources Load LC1 and Load LC2, see the chapter "9 - Touch protections", and the paragraph "
Current thresholds”, on page 91.
(2)
The Custom source is a combination of default events, that can be modified using the Ekip Connect
application so as to make the closing/opening of the contact correspond to a wide range of combinations
of the status bits of the release.
Continued on the next page