ABB | SACE Emax 2
Electronic accessories | 8 - Ekip Com DeviceNet modules
203 | © 2013
ABB |
1SDH001000R0002 - L7804
Connections
The modules must be mounted on the terminal box of the circuit-breaker or of the fixed part of
the withdrawable circuit-breaker, in the first free slot after the Ekip Supply module.
Information on the assembly is available from the web site http://www.abb.com/abblibrary/
DownloadCenter/, in particular with the kit sheet
The wiring diagrams for the modules are included below:
YO
01
H4
02
K5
04
K10
K9
94
92
H3
91
81
H2
82
K4
K8
84
74
K7
K3
H1
72
71
61
HC
62
64
54
52
51
EKIP Supply
Module
Trip Unit I/O
HC
K6
Ge-
Ge
Szc
K2
K1
W4
W3
R2
R1
Q4
Q3
Q2
Q1
YC2
YC
YU
YO2
RTC
I/O
TU
44
42
41
34
32
31
24
22
21
14
12
11
C22
C21
C12
C13
C11
C2
C3
C1
D2
D1
48
46
45
Ne
Rca
Ne-
Gzi
Szo
Szi
Gzo
Rct
Vn
V1
V2
V3
U2
U1
38
36
35
98
96
95
YR
M
S33
S51
EKIP Signalling 4K
Q5..Q10
Module
Module
HC
Ekip
Com
Devicenet
55
W7
W7
W8
(L)
(H)
BUS 1
W7
W8
W8
194
XK7
XK7
1
2
193
S75I/5
A4
A3
XV
X
X
A4
XV
* O)
K51
COM
* L), * M)
W8R
W8R
W7R
BUS 2
(H) (L)
W8R
W7R
W7R
Ekip
Com
R
Devicenet
K51
COM
* L), * M)
65
Diagrams 55 - 65
Further information is available on page 156, or on the site http://www.abb.com/abblibrary/
DownloadCenter/, where the wiring diagram is available
Termination resistor
The modules provide the possibility to insert a 120
Ω
termination resistor on the RS-485 bus,
by setting the dip-switches
Rterm
on the side of the modules, in position
on
. This option must
be selected before the installation of the modules.
For the positions
on
and
off
of the dip-switches
Rterm
, see the following figure (on DeviceNet
communication modules, the remaining dip-switches are not used).
ON
1 2 3 4
A
Figure 90
Access from the display
With the modules powered, and Local Bus enabled, the presence of the modules on the
terminal box activates additional menus on the display, to configure the modules according to
the characteristics of the network.
To enable the Local Bus, you need to select "On" in the menu
Settings
,
Modules
,
Local Bus
.
The following table illustrates the path for accessing the configuration parameters of the
modules from the display:
Settings
…
Network frequency
Modules
Local/Remote
Local Bus
…
Ekip Com DeviceNet
MAC Address
Baudrate
Ekip Com DeviceNet *R
MAC Address
Baudrate
…
Function
Power Controller
…
The following table illustrates configuration parameters of the modules:
Parameter
Values
Default
Description
MAC Address
1…63
• Ekip Com
DeviceNet: 63
• Ekip Com
DeviceNet
Redundant: 62
Address to be assigned to the modules.
IMPORTANT: devices connected
to the same network must have
different addresses.
Baudrate
125 kbit/s,
250 kbit/s,
500 kbit/s
125 kbit/s
Data transmission speed
NOTE:
the modules can also be configured with the Ekip Connect application (see
the chapter “13 - Other accessories", and the paragraph "Ekip Connect application"
on page 221).
The following table illustrates the path from the display for accessing information on the
modules:
Information
Protection unit
Circuit-breaker
Modules
…
Ekip DeviceNet
Ekip DeviceNet *R
…
Power Controller
The information on the modules that can be viewed includes the serial number and the software
version.