Putting into service and maintenance | 1 - Putting into service
Continued from the previous page
Accessories
(*)
to be
checked
Procedure
Closing coil with Ekip
Com Actuator
1. Power the protection release with the Vaux auxiliary power
supply.
2. Power the Ekip Com Actuator contacts.
3. Load the springs.
4. Select
“close CB”
from the Ekip Touch menu
Result: The circuit-breaker closes correctly; the signals are
normal.
NOTE!
The test can be performed if the protection
release and the coils are energized.
Lock for circuit-breaker
in open position (key or
padlock)
1. Open the circuit-breaker
2. Keep the opening push-button pressed
3. Turn the key and remove it
4. Attempt the circuit-breaker closing operation.
Result: Both manual and electrical closing are prevented.
Auxiliary contacts of the
circuit-breaker
1. Connect the auxiliary contacts to appropriate signalling
circuits or to the multimeter.
2. perform some closing and opening operations on the
circuit-breaker.
Result: signalling occurs normally.
Circuit-breaker
connected, isolated
for test, disconnected
auxiliary contacts
1. Connect the auxiliary contacts to appropriate signalling
circuits.
2. next bring the circuit-breaker to the connected, isolated for
test and disconnected position.
Result: the signals due to the relative operations are normal.
Interlocking devices of the
circuit-breaker connected
and extracted
(**)
1. Perform operating tests.
Result: the locks function correctly.
Interlock devices
between circuit breakers
assembled side by side
and stacked
1. Perform operating tests.
Result: the locks function correctly.
Device insertion and
extraction
(**)
1. Perform a few racking-in and racking-out operations.
Result: in the rack-in operation the circuit-breaker is
connected correctly. There is no particular resistance during
the first turns of the handle.
Auxiliary accessories and
auxiliary voltage
Verify the installation The value of the power supply auxiliary
voltage of the auxiliary accessories must be between 85% and
110% of the rated voltage for the auxiliary accessories.
Modules
1. Power the protection release
Result: Verify that Power LED is lit up on each accessory
present.
Make sure that the Local Bus communication line is activated
on the protection release.
External connections
1. In the case of Neutral external sensors, single-pole or
differential, to set the model and protection parameters
appropriately.
Result: No alarm present on the protection release.
WARNING!
During this phase the circuit-breaker
must be open and withdrawn (if withdrawable).
(*)
if present.
(**) only withdrawable versions.