ABB | SACE Emax 2
Ekip Dip protection release | 5 - List of alarms and signals
51 | © 2013
ABB |
1SDH001000R0002 - L7804
Continued from the previous page
HELP
Some led signals indicate connection errors or operational errors that require corrective or
maintenance operations. The following are the suggestions for checking referring to the
preceding LED table:
HELP note
Operation
A
Contact ABB.
B
Check the connections between release and accessories (rating plug,
trip coil, sensors, etc).
C
Normal operation/signalling provided by the release.
D
Error in setting of the dip-switches. Check and correct the following
conditions:
• All the dip-switches of L are in the ON position.
• I1 > I2 or I2 > I3.
• Iu < (2 * In * I1) in the case where InN = 200 %.
E
Carry out installation.
F
Connect via Ekip Connect in order to set the local bus or to confirm
maintenance.