ABB | SACE Emax 2
198 | © 2013
ABB |
1SDH001000R0002 - L7804
Electronic accessories | 7 - Ekip Com Profibus modules
Connections
The modules must be mounted on the terminal box of the circuit-breaker or of the fixed part of
the withdrawable circuit-breaker, in the first free slot after the Ekip Supply module.
Information on the assembly is available from the web site http://www.abb.com/abblibrary/
DownloadCenter/, in particular with the kit sheet
.
The wiring diagrams for the modules are included below:
YO
01
H4
02
K5
04
K10
K9
94
92
H3
91
81
H2
82
K4
K8
84
74
K7
K3
H1
72
71
61
HC
62
64
54
52
51
EKIP Supply
Module
Trip Unit I/O
HC
K6
Ge-
Ge
Szc
K2
K1
W4
W3
R2
R1
Q4
Q3
Q2
Q1
YC2
YC
YU
YO2
RTC
I/O
TU
44
42
41
34
32
31
24
22
21
14
12
11
C22
C21
C12
C13
C11
C2
C3
C1
D2
D1
48
46
45
Ne
Rca
Ne-
Gzi
Szo
Szi
Gzo
Rct
Vn
V1
V2
V3
U2
U1
38
36
35
98
96
95
YR
M
S33
S51
EKIP Signalling 4K
Q5..Q10
Module
Module
HC
XV
A4
X
X
XV
A3
A4
53
W5
W5
W6
(B)
(A)
W5
W6
W6
194
XK7
XK7
1
2
193
S75I/5
BUS 1
Ekip
Com
Pr
ofibus
COM
K51
O)
*
* L), * M)
* L), * M)
Ekip
Com
R
Pr
ofibus
BUS 2
W6R
W6R
W5R
(A) (B)
W6R
W5R
W5R
63
K51
COM
Diagrams 53 - 63
Further information is available on page 156, or on the site http://www.abb.com/abblibrary/
DownloadCenter/, where the wiring diagram is available
Termination resistors
The modules provide the possibility to insert a 220
Ω
termination resistor on the RS-485 bus,
by setting the dip-switches
Rterm
on the side of the modules, in position
on
.
In the event of termination of the bus, a 390
Ω
pull-up or pull-down resistor must also be
inserted on the lines, by setting the dip-switches
Rpoll
, in position
on
.
These options must be selected before installation of the modules.
For the positions
on
and
off
of the dip-switches, see the following figure.
ON
1 2 3 4
Figure 89