ABB | SACE Emax 2
Electronic accessories | 9 - Ekip Com Modbus TCP modules
207 | © 2013
ABB |
1SDH001000R0002 - L7804
Ekip RTC contact
The modules are always supplied with an Ekip RTC auxiliary contact, that supplies the release
with the signal indicating circuit-breaker ready to receive a close command.
Connections
The modules must be mounted on the terminal box of the circuit-breaker or of the fixed part of
the withdrawable circuit-breaker, in the first free slot after the Ekip Supply module.
Information on the assembly is available from the web site http://www.abb.com/abblibrary/
DownloadCenter/, in particular with the kit sheet
The wiring diagrams for the modules are included below:
YO
01
H4
02
K5
04
K10
K9
94
92
H3
91
81
H2
82
K4
K8
84
74
K7
K3
H1
72
71
61
HC
62
64
54
52
51
EKIP Supply
Module
Trip Unit I/O
HC
K6
Ge-
Ge
Szc
K2
K1
W4
W3
R2
R1
Q4
Q3
Q2
Q1
YC2
YC
YU
YO2
RTC
I/O
TU
44
42
41
34
32
31
24
22
21
14
12
11
C22
C21
C12
C13
C11
C2
C3
C1
D2
D1
48
46
45
Ne
Rca
Ne-
Gzi
Szo
Szi
Gzo
Rct
Vn
V1
V2
V3
U2
U1
38
36
35
98
96
95
YR
M
S33
S51
EKIP Signalling 4K
Q5..Q10
Module
Module
HC
XV
A4
X
X
XV
A3
A4
52
194
XK7
XK7
1
2
193
S75I/5
W9
RJ45
BUS 1
Ekip
Com
Modbus
TCP
n
COM
K51
O)
*
* L), * M)
* L), * M)
n
Ekip
Com
R
Modbus
TCP
BUS 2
RJ45
W9R
62
K51
COM
Diagrams 52 - 62
Further information is available on page 156, or on the site http://www.abb.com/abblibrary/
DownloadCenter/, where the wiring diagram is available
Access from the display
With the modules energized, and the Local Bus enabled, the presence of the modules on the
terminal box activates additional menus on the display:
• In order to set the addressing of the modules.
• In order to display information on the modules.
To enable the Local Bus, you need to select "On" in the menu
Settings
,
Modules
,
Local Bus
.
The following table illustrates the path from the display to set addressing for the modules:
Settings
…
Network
frequency
Modules
Local/Remote
Local Bus
…
Ekip Com Modbus TCP
Force Static IP address
Static IP Address
Static Network Mask
Static Gateway Address
Ekip Com Modbus TCP
*R
(1)
…
Function
Power
Controller
…
(1)
Like the Ekip Com Modbus TCP menu.
The following table illustrates the parameters for setting the addressing of the modules: For
further information, see the table on page 208.
Parameter
Selectable values Default
Description
Force Static IP
address
Off, On
Off
• Off = Dynamic IP address.
• On = Static IP address.
Static IP Address
Displayed with static IP Address enabled, it must be selected in
order to insert the IP Address of the modules.
Static Network Mask
Displayed with static IP Address enabled, it must be selected in
order to insert the subnet mask of the modules.
Static Gateway
Address
Displayed with static IP Address enabled, it must be selected in
the presence of multiple subnets, in order to insert the IP Address
of the node to which the modules are connected.
The following table illustrates the path from the display for accessing information on the
modules:
Information
Protection unit
Circuit-breaker
Modules
…
Ekip Com Modbus TCP
Ekip Com Modbus TCP *R
…
Power Controller
Continued on the next page