Electronic accessories | 11 - Ekip Link module
Access from the display
With the module energized, and the Local Bus enabled, the presence of the module on the
terminal box activates additional menus on the display :
• To set the addressing of the module.
• To display information on the module.
To enable the Local Bus, you need to select "On" in the menu
Settings
,
Modules
,
Local Bus
.
The following table illustrates the path from the display to set addressing of the module:
Settings
…
Network frequency
Modules
Local/Remote
Local Bus
…
Ekip Link
Force Static IP
address
Static IP Address
Static Network Mask
Static Gateway
Address
…
Function
Power Controller
…
The following table illustrates the parameters for setting the addressing of the modules: For
further information, see the table on page 217.
Parameter
Selectable values
Default
Description
Force Static IP address
Off, On
Off
• Off = Dynamic IP address.
• On = Static IP address.
Static IP Address
Displayed with static IP Address enabled, it must be selected in
order to insert the IP Address of the module.
Static Network Mask
Displayed with static IP Address enabled, it must be selected in
order to insert the subnet mask of the module.
Static Gateway Address
Displayed with static IP Address enabled, it must be selected
in the presence of multiple subnets, in order to insert the IP
Address of the node to which the module is connected.
The following table illustrates the path from the display for accessing information on the
modules:
Information
Protection unit
Circuit-breaker
Modules
…
Ekip Link
…
Power Controller
Continued on the next page