Emax E2.2-E4.2-E6.2 circuit-breakers | 6 - Installation
Reversal of the position of the
vertical/horizontal terminals
If the circuit-breaker is supplied equipped with terminals of the horizontal/rear type, it is possible
at any moment to switch from horizontal to vertical and vice versa. (see Figure 56 and Figure
57). Lock the screws with the following tightening torques:
• E2.2 - M6 screws - Tightening torque 8.6 Nm
• E4.2 and E6.2 - M8 screws - Tightening torque 20 Nm
Figure 56