ABB | SACE Emax 2
Ekip Touch protection release | 1 - Layout of the interface
57 | © 2013
ABB |
1SDH001000R0002 - L7804
Signallings
The following table provides a description of the signals of the interface:
LED
Description
Green
The possible states are:
• Off: power supply absent.
• On, fixed or flashing: power supply present, and release on.
Yellow
The possible states are:
• Off: no warning or error.
• On, flashing quickly: absence of communication with the Mainboard, or
installation error (of the Rating Plug, Ekip Measuring or Ekip Measuring Pro
module).
• On, flashing slowly: internal error.
• On, with two quick flashes every 0,5 s: parametrization error.
• On, fixed: prealarm of protection L, or circuit-breaker status error.
Red
The possible states are:
• Off: no alarm or error.
• On, flashing quickly: absence of communication with the Mainboard, or trip
coil disconnected, or current sensor disconnected, or delay active.
• On, with two quick flashes every 2 s: Rating Plug error.
• On, flashing slowly: internal error.
• On, fixed: signal that opening has occurred.
Structure of the pages
The following table illustrates how the pages shown on the display are structured:
Level 1
Level 2
Level 3
Diagnosis bar.
Alarm list
page
Main page
Histograms
page
Menu
page
Basic protections
menu
Advanced protections
menu
Measurements
menu
Settings
menu
Test
menu
Information
menu
Measuring instruments
pages
Measurements
pages
NOTE:
the level 3 pages are not graphical pages, and are dealt with in chapter “6 -