ABB | SACE Emax 2
280 | © 2017 ABB | 1SDH001330R0002 - ECN000058721 Rev. A
Mechanical accessories | 5 - Operating mode for E1.2
Continued from the previous page
5. Turn the crank clockwise until the pushbutton comes out and the indicator shows that the circuit-
breaker is in
TEST
position. See Figure 84.
Figure 84
6. Press the lock button and then rotate the crank clockwise until the button comes out and the indicator
shows that the circuit-breaker is in the
CONNECT
position. See Figure 85.
2
1
Figure 85
7. Extract the crank. See Figure 86.
8. Replace the crank in its housing See Figure 87.
Figure 86
Figure 87
Continued on the next page