ABB | SACE Emax 2
Ekip Dip protection trip unit | 3 - Measurements
27 | © 2017 ABB | 1SDH001330R0002 - ECN000058721 Rev. A
3 - Measurements
Introduction Measurements
The Ekip Dip trip unit records various items of information, useful for analysis and consultation:
• Instantaneous measurements of phase currents
• Measurement of the maximum and minimum currents recorded with an adjustable interval
• Trip Log
• List of events, changes of state and alarms recorded by the trip unit
• Contact Wear value
• Number of mechanical and electrical operations.
NOTE:
all the information is available with Ekip T&P and Ekip Bluetooth modules and with
the Ekip Connect software. The instantaneous measurements are also available with the Ekip
Multimeter switchgear unit.
Instantaneous currents
The following table summarises the measurements of the instantaneous currents:
Type of Measurement
Range
Standard operation range
Accuracy
Phase currents (I1, I2, I3, INe)
0.03…16 In
0.2…1.2 In
1 %
NOTE:
the precisions specified in the table refer to the range of normal operation
Maximum and minimum
currents
The trip unit is able to record the maximum and minimum current, measured inside an interval that can be
programmed by the user.
Every measurement recorded is accompanied by the following information:
• Recording interval.
• Phase and value of maximum and minimum current measured.
• Date and time of the recording (referring to the internal clock).
NOTE:
in the case of the minimum current, if the value drops below the 0.03 In threshold, it
will be recorded and represented by the symbol “…” in the measurement field.
Trips
The trip unit is able to record the last 30 openings of the circuit-breaker caused by protection functions (trips).
The trips include useful information:
• The protection that caused the trip
• The progressive number of the opening
• The date and time of the opening (referring to the internal clock)
• The measurements associated to the trip protection.
Contact Wear
Contact wear indicates the state of deterioration of the main contacts of the circuit-breaker.
The value is expressed as a percentage, and is 0 % in the case of no wear, and 100 % in the case of total
wear.
The contact wear is calculated automatically by the trip unit at every opening for protection or, in the presence
of an auxiliary power supply, also at every manual opening of the circuit-breaker.
Number of operations
In the presence of auxiliary power, the trip unit records a series information relating to the openings of the
circuit-breaker:
• Number of manual operations
• Total number of operations ( trips)
Summary of Contents for SACE Emax E1.2
Page 2: ...ABB SACE Emax 2 2 2017 ABB 1SDH001330R0002 ECN000058721 Rev A ...
Page 8: ...VI 2017 ABB SACE Emax 2 1SDH001330R0002 ECN000058721 Rev A ...
Page 9: ...ABB SACE Emax 2 3 2017 ABB 1SDH001330R0002 ECN000058721 Rev A ...
Page 310: ...ABB SACE Emax 2 304 2017 ABB 1SDH001330R0002 ECN000058721 Rev A Service 1 Power Care ...