Ekip Dip protection trip unit | 6 - Ekip Dip: additional functions
Circuit-breaker label and user
Data
Labels that can be configured by the user so as to facilitate remote identification of the trip unit; in detail the
CB label
, the trip unit model and the communication address form the identifier used by Ekip Connect for
the devices connected.
Info Page
Additional information page that can be activated and customized by the user. If activated, it can be accessed
on the display by pressing the iTest button twice from the main page.
NOTE:
the pages can be configured with all the trip units for SACE Emax 2 circuit-breakers,
but they can only be displayed via Ekip Touch.
Date of installation
Installation date of the circuit-breaker.
Load Profile Timers
SACE Emax 2 has 4 counters which display how long the maximum current measured has remained in each
percentage band.
The counters are expressed in seconds and the bands are: 0-49%In, 50-79%In, 80-89%In, >90%In.
Energy Store Time
The counter indicates the time that has elapsed since the last energy metering reset.
It is active and updated in the presence of at least one of the following: auxiliary supply, supply by Ekip T&P
or supply by Ekip Measuring.
Led Alive
The parameter allows the behaviour of the power-on LED indicator of the trip unit and of all modules that can
be connected to Ekip Supply to be changed. If activated:
• Trip unit: it comes on at a frequency of 0.5 Hz.
• Modules connected to Ekip Supply: if there are no communication errors, they synchronize with the flashes
of the trip unit LED.
If deactivated, the power-on leds on the respective devices come on with a steady light.
Open/Close Remote Direct
Command
The parameter controls two different command packages for remote circuit-breaker opening and closing:
•
Enabled
: commands 7 and 8 are valid (direct commands for
CB Open
and
CB Close
).
•
Disabled
: commands 7 and 8 are not valid.
IMPORTANT: in this case, remote circuit-breaker opening and closing can still be
obtained using the programmable YC COMMAND and YO COMMAND functions and
the Request circuit-breaker opening (28) and Request circuit-breaker closing (29)
commands.
Modules network settings
retention
It allows the communication parameters of the circuit-breaker to be controlled if the trip unit is replaced:
•
Overwrite
: the parameters of the new trip unit are valid, so it is advisable to make sure that the communication
parameter settings suit the communication network.
•
Keep module data
: the new trip unit updates its communication parameters with the ones in the Ekip
Com modules of the circuit-breaker, used up to that moment in the various communication networks.
The trip units are supplied with the parameter set as
Overwrite
.
Wink
The command allows the power-on LED on the protection trip unit to flash at 3 Hz so as to physically identify
a trip unit that would not be identifiable in other ways.
3 Hz flashing is disabled by sending another
Wink
command or by switching off the trip unit.
Glitch
The commands of
Glitch
16 to 23 activate the respective glitch registers, which can be used for customizing
programmable functions or output contacts.
Summary of Contents for SACE Emax E1.2
Page 2: ...ABB SACE Emax 2 2 2017 ABB 1SDH001330R0002 ECN000058721 Rev A ...
Page 8: ...VI 2017 ABB SACE Emax 2 1SDH001330R0002 ECN000058721 Rev A ...
Page 9: ...ABB SACE Emax 2 3 2017 ABB 1SDH001330R0002 ECN000058721 Rev A ...
Page 310: ...ABB SACE Emax 2 304 2017 ABB 1SDH001330R0002 ECN000058721 Rev A Service 1 Power Care ...