Ekip Touch protection trip unit | 6 - Menu
Continued from the previous page
Measurements
Options
Trip units
Maintenance
•
Contact Wear
: it shows the estimated percentage of wear on the
contacts
•
Last Service Contact Wear
: it shows the percentage of contact
wear at the last maintenance
•
Installation
: it shows the installation date of the circuit-breaker.
•
Last Maintenance
: it shows the date of the last maintenance.
• Service RESET: it updates the values of the parameters
Last
Service Contact Wear
and
Last Maintenance
, with the percentage
of contact wear and the date set on the trip unit at the moment of the
command selection.
Touch
G-Touch
Hi-Touch
G Hi-Touch
(1)
Measurements available with Ekip Measuring or Ekip Measuring Pro modules.
(2)
Measurements available with Ekip Synchrocheck module.
(3)
Measurements available with the Network Analyzer function enabled (see the menu Settings - Network
Analyzer).
Last Trip measurements
To open the page, from the menu
Measurements
, you need to select
Historicals
-
Tripping
, and a trip from
the list.
Alternatively, if the main page or a level 2 page is displayed (see the chapter “1 - Layout of the interface", and
the paragraph "Structure of the pages”, on page 38), you can open the page relating to the last opening by
pressing the
iTEST
key until the page is displayed.
NOTE:
when a trip occurs, the page relating to the last trip is opened automatically.
The page shows details related to the selected opening.
To exit the page, press the
iTEST
key. Now the page is open.
The page appears as follow:
1885.5A
L3
L2
L1
1903.1A
. . . .
14:07:13:406
Ne
n°01
A
B
C
D
E
F
Last Trip
L Protection
Mar 04, 2013
Figure 13
The following table provides a description of the various areas of the page:
Pos.
Description
A
Name of the page.
B
Time at which the selected trip occurred (time set on the trip unit at the moment of the trip)
C
Date at which the selected trip occurred (date set on the trip unit at the moment of the trip)
D
The protection that tripped.
E
Number of the selected trip.
NOTE
:
every new trip is associated to an incremental number
F
Measurements recorded at tripping.
Summary of Contents for SACE Emax E1.2
Page 2: ...ABB SACE Emax 2 2 2017 ABB 1SDH001330R0002 ECN000058721 Rev A ...
Page 8: ...VI 2017 ABB SACE Emax 2 1SDH001330R0002 ECN000058721 Rev A ...
Page 9: ...ABB SACE Emax 2 3 2017 ABB 1SDH001330R0002 ECN000058721 Rev A ...
Page 310: ...ABB SACE Emax 2 304 2017 ABB 1SDH001330R0002 ECN000058721 Rev A Service 1 Power Care ...