82 | © 2017 ABB | 1SDH001330R0002 - ECN000058721 Rev. A
Ekip Touch protection trip unit | 11 - Hi-Touch protections
S2 Protection
I5
t
t5
I
S2
Path
Main page - Menus - Protections
Function
S2 protection:
• It protects against a selective short circuit, as the S function.
• It is independent from S protection: it is therefore possible to program thresholds and functions of the two
protections in order to have different installation solutions (for example: signalling with S and trip with S2,
or vice versa, or S and S2 both for signalling or trip).
When the activation threshold is exceeded, the protection trips within a fixed time. The user can set the
threshold and the tripping time.
Parameters
Here is a list of the available parameters:
Parameter
Description
Enable
To activate/deactivate the protection.
Threshold I5
It defines the current value that activates the protection when exceeded (with
reference to the figure above, the threshold is the part of the curve parallel to
the y-axis).
It is represented both as an absolute value (Ampere) and as a relative value (In,
nominal value defined by the Rating Plug).
IMPORTANT: The I5 threshold set must be higher than the I1
threshold. An incorrect configuration gives an error on the display
and the programming session doesn’t conclude, with consequent
rejection of the changes made to the parameters.
Time t5
This is the delay time between the exceeding of the I5 threshold and the
sending of the opening command.
S2 protection has
Trip Enable, Zone Selectivity, Startup Enable
, see page 88.
Via Ekip Connect it is also possible to access the
blocking functions
, see page 72.
Summary of Contents for SACE Emax E1.2
Page 2: ...ABB SACE Emax 2 2 2017 ABB 1SDH001330R0002 ECN000058721 Rev A ...
Page 8: ...VI 2017 ABB SACE Emax 2 1SDH001330R0002 ECN000058721 Rev A ...
Page 9: ...ABB SACE Emax 2 3 2017 ABB 1SDH001330R0002 ECN000058721 Rev A ...
Page 310: ...ABB SACE Emax 2 304 2017 ABB 1SDH001330R0002 ECN000058721 Rev A Service 1 Power Care ...