ABB | SACE Emax 2
Electronic accessories | 3 - Ekip Measuring modules
181 | © 2017 ABB | 1SDH001330R0002 - ECN000058721 Rev. A
Measurements
The following table lists the measurement accuracy for the modules:
Quantity
Range
Accuracy
Phase-to-phase voltage
(1)
100…1150 V AC
± 0.5 % @ 45…66 Hz
Frequency
(2)
30…80 Hz
± 0.1 %
(3)
(1)
With phase-to-phase voltage V greater than 690 V AC rated voltage (maximum 760 V AC), in the presence of
external sockets and an isolation transformer.
(2)
The measurement of the frequency is available with a a phase-to-phase voltage value
≥
36 V AC, and is
unavailable with a phase-to-phase voltage value
≤
32 V AC.
(3)
In the absence of harmonic distortion.
Connections
The modules must be mounted directly on the Mainboard, to the right of the trip unit. In parallel they are
connected to a connector, to which the phase and neutral voltages arrive either on the internal contacts of
the circuit-breaker, or on the external sockets.
Information on the assembly is available on the website http://www.abb.com/abblibrary/DownloadCenter/, in
particular in the kit sheet
IMPORTANT: in the case of dielectric tests, you need to disconnect the modules as
illustrated in the assembly diagram, and to disconnect the external sockets from the
terminal box. It is not necessary to remove the modules.
An example with an E2.2 circuit-breaker in fixed and withdrawable versions is provided to the side.
The following is a view of the terminal box of E1.2 and E2.2-E4.2-E6.2 circuit-breakers with the relevant wiring
diagram:
R2
R1
U2
U1
38
36
35
98
96
95
YR
M
S33
S51
YO
EKIP Supply
Trip Unit I/O
Ge-
Ge
Szc
K2
K1
W4
W3
Q4
Q3
Q2
Q1
YC
YU
YO2
RTC
I/O
TU
44
42
41
34
32
31
24
22
21
14
12
11
C12
C13
C11
C2
C3
C1
D2
D1
48
46
45
Ne
Rca
Ne-
Gzi
Szo
Szi
Gzo
Rct
Vn
V1
V2
V3
Module
Module
YO
01
H4
02
K5
04
K10
K9
94
92
H3
91
81
H2
82
K4
K8
84
74
K7
K3
H1
72
71
61
HC
62
HC
64
54
52
51
Trip Unit I/O
HC
K6
Ge-
Ge
Szc
K2
K1
W4
W3
R2
R1
Q4
Q3
Q2
Q1
YC2
YC
YU
YO2
RTC
I/O
TU
44
42
41
34
32
31
24
22
21
14
12
11
C22
C21
C12
C13
C11
C2
C3
C1
D2
D1
48
46
45
Ne
Rca
Ne-
Gzi
Szo
Szi
Gzo
Rct
Vn
V1
V2
V3
U2
U1
38
36
35
98
96
95
YR
M
S33
S51
EKIP Signalling 4K
Q5..Q10
Module
Module
Module
EKIP Supply
20
V1
V1
V2
V2
V3
V3
VN
VN
L3
L2
L1
N
XV
XV
A4
X
A1
X
A4
L1 L2 L3
VN
VN
V3
V3
V2
V2
V1
V1
N
21
Ekip Measuring Pr
o
Ekip Measurin
g
Ekip
M
easuring Pr
o
Ekip Measurin
g
MEAS
K51
K51
MEAS
L3
L2
L1
N
A3
B3
a3
b3
A2
B2
a2
b2
TU1
A1
B1
a1
b1
23
Ekip Measuring Pr
o
Ekip Measurin
g
MEAS
K51
VN
VN
V3
V3
V2
V2
V1
V1
E)
*
Ekip
M
easuring Pr
o
22
V1
V1
V2
V2
V3
V3
VN
VN
L3
L2
L1
K51
MEAS
L3
L1 L2
GS
PE
3~
AB)
*
Diagrams 20 - 21 - 22 - 23
Further information is available on page 174, or on the website http://www.abb.com/abblibrary/
DownloadCenter/, where the wiring diagram is available
Access from the display
With the trip unit energized, the presence of the modules activates the following on the display:
• Additional graphical pages, that display measurements.
• Additional menus.
The additional graphical pages are:
• A summary of the measurements in progress (maximum phase current, maximum phase-to-phase voltage,
power factor, and the active, reactive and apparent power), accessible from the page
Histograms
(see
page 42).
• The indicators of the maximum phase-to-phase voltage, and of the active, reactive and apparent power,
accessible by selecting the pages
Measuring instruments
• The measurements of the phase and phase-to-phase voltages, and of the active, reactive and apparent
power, as well as the energy counters, accessible by selecting the pages
Measurements
(see page 45).
• The historicals of the minimum and maximum phase-to-phase voltages and maximum and mean power,
accessible from the menu
Measurements
.
• The waveforms and the harmonics of the phase-to-phase voltages, accessible from the menu
Measurements
.
The additional menus allow you to:
• Configure the protections activated by Ekip Measuring Pro.
• Configure the modules.
• Display the measurements associated to the modules (in addition to those displayed in the graphical pages).
• Display information on the modules.
The following table shows the path from the display to access the configuration parameters of the protections
activated by the Ekip Measuring Pro module:
Advanced
…
IU Protection
Rc Protection
(1)
UV Protection
UV2 Protection
OV Protection
OV2 Protection
RV Protection
VU Protection
UF Protection
UF2 Protection
OF Protection
OF2 Protection
ROCOF Protection
RP Protection
RQ Protection
OP Protection
OQ Protection
UP Protection
Synchrocheck Protection
Signallings
Phase Sequence
Cos
Ø
Current thresholds
…
(1)
Protection available with Rating Plug Rc and Ekip Measuring Pro, and toroid Rc (see the menu Settings -
Circuit Breaker - Ground protection), and alternative to the Gext protection (see the Protections menu).
Continued on the next page
Summary of Contents for SACE Emax E1.2
Page 2: ...ABB SACE Emax 2 2 2017 ABB 1SDH001330R0002 ECN000058721 Rev A ...
Page 8: ...VI 2017 ABB SACE Emax 2 1SDH001330R0002 ECN000058721 Rev A ...
Page 9: ...ABB SACE Emax 2 3 2017 ABB 1SDH001330R0002 ECN000058721 Rev A ...
Page 310: ...ABB SACE Emax 2 304 2017 ABB 1SDH001330R0002 ECN000058721 Rev A Service 1 Power Care ...