L2275
Emax UL
86/132
Doc. N°
Mod.
RH0109002
Apparatus
Scale
Page N°
N.B.
Incorrect configuration of In and Un does not jeopardize perfect functionality of the protections in any way, (except, possibly, selection of threshold
G).
The only problem will be display of an incorrect absolute value of Currents, Voltages and Powers.
Properties/function
Values selectable
Language
Engl. (English), Ital. (Italian), Fran. (French), Deut. (German) Espa. (Spanish)
Net Frequency
50Hz, 60Hz
Neutral sel.
50%, 100%, 150%, 200%
Toroid Selec.
Int (internal, Ext (external)
Ext. tor. In
100A, 250A, 400A, 800A
C.B.
Versions allowed in the catalogue
CS In
250A, 400A, 800A, 1000A, 1200A, 1600A, 2000A, 2500A, 3200A, 3600A, 4000A, 5000A
VS Un
[100, 115, 120, 190, 208, 220, 230, 240, 277, 347, 380, 400, 415, 440, 480, 500, 550, 600, 660, 690,
910, 950, 1000] /
√
3 V
Password
0000…9999
Store Meas. T.
[5, 15, 30, 60, 120] minutes
Warning current Th. ‘——’(off), 0.3 …. 3.0 x In step 0.05 x In
PR020/K
On , Off
PR020/K relays,
PR113 relays 1 e 2
See par. 15.2.10.1
Select what information to combine with the 7 clean contacts present on the PR020/K. Selection is only
possible if the accessory unit is configured as present on the PR113. The selections possible are given
in par. 15.2.10.1. The PR020/K must be set to operate in “Configurable from PR113” mode by means
of special dip-switches (only with Vaux).
Programming new password in EDIT mode. The successive messages are:
New Password:
→
→
→
→
→
[****] e Confirm PSW :
→
→
→
→
→
[****] for confirmation.
Select the time interval for data acquisition in the Historical Measurements.
Select the Warning current threshold value (Iw) (the absolute value of the threshold is also displayed).
Indicate whether there is an PR020/K accessory unit (can only be set with Vaux).
Select what information to combine with the 2 clean contacts (K51/p1 and K51/p2) present on the
PR113/P-A (see par. 15.2.10.1).
Select the type of protection against ground fault: select [Int ] if you want to protect the installation with the
help of the internal toroid, otherwise [Ext ] if you want to protect with the help of the external toroid by making
the “Source Ground Return” protection function.
Select the value of the continuous current rating of the external toroidal transformer for the “Source Ground
Return” function.
Select the type of EMAX power circuit breaker (code and continuous current rating) on which the PR113
unit is mounted. The selections possible are available in the technical catalogue.
Select the value of the continuous current rating of the current sensors (CS) mounted on the power circuit
breaker.
Select the rated voltage of the voltage sensors (VT) installed for the power circuit breaker.