5.6.
SACE PR010/K with SACE PR113 unit
5.6.1. Dip-switch settings
N°
Dip-Sw
Description of
dip-switch
0 (Off)
1 (On)
Note
1
Test
Normal
Self-test
For normal functioning mode, set this dip-
switch to OFF.
2
K51/1
Configuration
A
Alarm
protection L
B
Pre-alarm function
L
3
K51/4
Configuration
A
Alarm
protection G
B
Under voltage coil
activated
4
K51/5
Configuration
A
Bus KO
B
Internal overheat
if dip-switch N°5 = Off
Note “§§§”:
Functions (A or B)
assigned to relay contact, to be selected with
corresponding dip-switch
5
K51/1…K51/8
Configuration
(See note “§§§”)
Bus KO
(See note “***”)
if dip-switch N°5 = On
Note “***”:
The functions assigned to contacts
(K51/1…K51/4 e K51/6…K51/8)
are those directly defined by the user on PR113
while contact K51/5 is associated with the
signalling of “bus KO”
6
Mode
Slave
Master
Master if PR113/P + PR010/K.
Slave if PR113/PD + PR010/K.
7
Baud Rate
19.2 kit/s
38.4 kbit/s
Set 38.4 kbit/s
8
State
Normal
Stand-by
For normal functioning mode, set this dip-
switch to OFF.
Example of dip-switch settings for connection of PR010/K unit with SACE PR113/P protection unit.
Dip-switch n°
1
2
3
4
5
6
7
8
Off
On