5.7.
SACE PR010/K with SACE PR212/P unit
5.7.1. Dip-switch settings
N°
Dip-Sw
Description of
dip-switch
0 (Off)
1 (On)
Note
1
Test
Normal
Self-test
For normal functioning mode, set this dip-switch to OFF.
2
3
4
5
-
-
-
Not used
6
Mode
Slave
Master
Master if PR212/P + PR010/K
Slave if PR212/P +
PR212/D-L (or PR212/D-M) + PR010/K
7
Baud Rate
19.2 kbit/s
38.4 kbit/s
Set 38.4 kbit/s
8
State
Normal
Stand-by
For normal functioning mode, set this dip-switch to OFF.
Example of dip-switch settings for connection of PR010/K with SACE PR212/P protection unit.
1
2
3
4
5
6
7
8
5.7.2. Signalling
The significance of signals (K51/1…K51/8) for the SACE PR212/P protection unit is as follows:
Contact
N° Pin on
unit PR010/K
Event which causes closing of relay
K51/1
5
Alarm protection L (overload)
K51/2
6
Alarm protection S (selective short circuit)
K51/3
7
Alarm protection I (instantaneous short circuit)
K51/4
8
Alarm protection G (ground fault)
K51/5
9
Internal Bus communication problem (bus KO)
K51/6
10
Not Used
K51/7
12
CB trip alarm –TRIP–
K51/8
17
Pre-alarm function L (overload)
Off
On