background image

Rev.

L0633

Apparatus

SACE PR010/K

Sh. No.

Mod.

Apparecchio

N° Pag.

ÿþþ

ABB SACE

Doc. No.
N° Doc

RH0043.002

Sh. No
N° Pag..

9

/

20

5.3.1. Example of dip-switch setting

Example of dip-switch setting for the connection of PR010/K with protection unit PR112/P with last letter of serial
number from A to F (see par.5.4).

Test

:O

ff

K51 Configuration :

not used

Mode

:

Ma

st

er

Ba

ud

:

19.2

kbit/s

State

:O

ff

5.3.2. Default settings

The PR010/K unit is supplied by ABB SACE with the following parameters pre-set:

Dip-Sw n°

Description of

dip-switch

Value set

1

Test

Off (Deactivated)

2
3
4
5

K51 Configuration

Dip-switch set in position A (Off)

6

Mode

Slave

7

Baud

19.2 kbit/s

8

State

Normal

5.3.3. Serial Number

The Serial Number label is positioned on the left side, at the top.

Off (0)

On (1)

1

2

3

4

5

6

7

8

Dip-switches for setting of

functioning mode.

PR010/K Top view

Summary of Contents for SACE PR010/K

Page 1: ...SIGNALLING UNIT SACE PR010 K Title titolo Manuale d uso Lang Lingua IT Rev L0633 Apparatus SACE PR010 K Scale Mod Apparecchio Scala ÿþþ ABB SACE Doc No N Doc RH0043 002 Sh No N Pag 1 20 ...

Page 2: ...h setting 9 5 3 2 Default settings 9 5 3 3 Serial Number 9 5 4 SACE PR010 K WITH SACE PR112 UNIT WITH LAST LETTER OF SERIAL NUMBER A E 10 5 4 1 Dip switch settings 10 5 4 2 Signalling 10 5 5 SACE PR010 K WITH SACE PR112 UNIT WITH LAST LETTER OF SERIAL NUMBER F Z 11 5 5 1 Dip switch settings 11 5 5 2 Signalling 11 5 6 SACE PR010 K WITH SACE PR113 UNIT 12 5 6 1 Dip switch settings 12 5 6 2 Signallin...

Page 3: ...lowing documents must be consulted Sheet kit protection unit PR212 P doc n RH0062 Sheet kit protection unit PR212 MP doc n RH0063 Instruction manual protection unit PR112 P doc n RH0288 for version IEC or RH0109 per version UL Instruction manual protection unit PR113 P doc n RH0288 for version IEC or RH0109 for version UL ABB SACE Isomax technical catalogue ABB SACE Emax technical catalogue 1 2 Ap...

Page 4: ... see IEC 478 1 CEI 22 3 not greater than 3 5mA IEC 60364 41 and CEI 64 8 2 2 Mechanical characteristics Casing Metallic 1mm sheet Degree of protection IP20 Dimensions 100 x 45 x 120 mm h x w x d Weight 500 gr including 2 front connectors 2 3 Environmental conditions Operating environmental temperature 5 C 70 C Storage conditions 40 C 90 C 2 4 Communication Bus Exclusive ABB SACE communication bus ...

Page 5: ... G green LED Tx Int Bus yellow Off Contact K51 1 open Contact K51 2 open Contact K51 3 open Contact K51 4 open anomalous situation On Contact K51 1 closed Contact K51 2 closed Contact K51 3 closed Contact K51 4 closed anomalous situation Fast flashing OK Flashing with freq 2Hz see Flashing at 2Hz one of the following can be verified Communication not present SACE PR010 K in stand by mode or Self t...

Page 6: ...51 to rest conditions contacts open following switching contacts closed for protection function trip This reset can be carried out carrying out a reset see par 4 1 if the applicable scenario is PR010 K in Master mode see par 1 2 sending a Trip Reset command from the remote supervision system pressing the RESET push button on the front of the unit if the applicable scenario is PR010 K in Slave mode...

Page 7: ... mm2 fitted with an eye terminal connected to the M4 bolt fitted to the rear of the casing An earth terminal is provided on a front terminal to connect the electronic circuit to the installation earth This terminal must not be connected to the case earth bolt Dielectrical rigidity tests must not be carried out on the inputs and outputs of the PR010 K unit Even if the unit can be installed with the...

Page 8: ...pending upon the type of protection unit connected to the PR010 K unit the event associated with the switching of some contacts K51 can be selected from two alternatives A or B N B For some protection units an alternative which can be selected using the dip switches is not provided in this case the event associated with each contact is unique defined by ABB SACE and is independent of the position ...

Page 9: ...Configuration not used Mode Master Baud 19 2 kbit s State Off 5 3 2 Default settings The PR010 K unit is supplied by ABB SACE with the following parameters pre set Dip Sw n Description of dip switch Value set 1 Test Off Deactivated 2 3 4 5 K51 Configuration Dip switch set in position A Off 6 Mode Slave 7 Baud 19 2 kbit s 8 State Normal 5 3 3 Serial Number The Serial Number label is positioned on t...

Page 10: ...ate Normal Stand by For normal functioning mode set this dip switch to OFF Example of dip switch settings for connection of PR010 K unit with SACE PR112 P protection unit Dip switch n 1 2 3 4 5 6 7 8 5 4 2 Signalling The significance of signals K51 1 K51 8 for protection unit SACE PR112 is as follows Contact N Pin on unit PR010 K Event which causes closing of relay K51 1 5 Alarm protection L overl...

Page 11: ... Stand by For normal functioning mode set this dip switch to OFF Example of dip switch settings for connection of PR010 K unit with SACE PR112 P protection unit Dip switch n 1 2 3 4 5 6 7 8 5 5 2 Signalling The significance of signals K51 1 K51 8 for protection unit SACE PR112 is as follows Contact N Pin on unit PR010 K Event which causes closing of relay K51 1 5 Alarm protection L overload K51 2 ...

Page 12: ... if dip switch N 5 Off Note Functions A or B assigned to relay contact to be selected with corresponding dip switch 5 K51 1 K51 8 Configuration See note Bus KO See note if dip switch N 5 On Note The functions assigned to contacts K51 1 K51 4 e K51 6 K51 8 are those directly defined by the user on PR113 while contact K51 5 is associated with the signalling of bus KO 6 Mode Slave Master Master if PR...

Page 13: ... bus KO Load check LC1 K51 6 10 Configured by user on PR113 unit CB trip alarm TRIP K51 7 12 Configured by user on PR113 unit Load check LC2 K51 8 17 Configured by user on PR113 unit The reason for the closing of these contacts K51 1 K51 4 and K51 5 depends upon the configuration event A or event B set via the dip switch of the PR010 K unit only if dip sw N 5 is set to OFF see par 5 6 1 In the cas...

Page 14: ...tate Normal Stand by For normal functioning mode set this dip switch to OFF Example of dip switch settings for connection of PR010 K with SACE PR212 P protection unit 1 2 3 4 5 6 7 8 5 7 2 Signalling The significance of signals K51 1 K51 8 for the SACE PR212 P protection unit is as follows Contact N Pin on unit PR010 K Event which causes closing of relay K51 1 5 Alarm protection L overload K51 2 6...

Page 15: ...to OFF Example of dip switch settings for connection of PR010 K unit with SACE PR212 MP protection unit 1 2 3 4 5 6 7 8 5 8 2 Signalling The significance of signals K51 1 K51 8 for the SACE PR212 MP protection unit is as follows Contact N Pin on unit PR010 K Event which causes closing of relay K51 1 5 Alarm protection L overload K51 2 6 Alarm protection R rotor stuck K51 3 7 Alarm protection I ins...

Page 16: ...Rev L0633 Apparatus SACE PR010 K Sh No Mod Apparecchio N Pag ÿþþ ABB SACE Doc No N Doc RH0043 002 Sh No N Pag 16 20 5 9 Applicable electrical diagrams 5 9 1 PR112 or PR113 PR010 K ...

Page 17: ...Rev L0633 Apparatus SACE PR010 K Sh No Mod Apparecchio N Pag ÿþþ ABB SACE Doc No N Doc RH0043 002 Sh No N Pag 17 20 5 9 2 PR113 P 3 PR010 K units ...

Page 18: ...Rev L0633 Apparatus SACE PR010 K Sh No Mod Apparecchio N Pag ÿþþ ABB SACE Doc No N Doc RH0043 002 Sh No N Pag 18 20 5 9 3 PR212 P or PR212 MP PR010 K 5 9 4 PR212 P PR212 D L or PR212 D M PR010 K ...

Page 19: ...10 K X3 X4 Connectors for auxiliary circuits of protection unit PR212 P or PR212 MP X Connector for auxiliary circuits for removable breaker XV Terminals for auxiliary circuits for fixed breaker 6 Troubleshooting The following table details a range of typical operational situations useful in the understanding and resolution of hypothetical faults and malfunctions NB Before consulting the following...

Page 20: ...on not present 2 Unit PR010 K in Stand by mode 3 Unit PR010 K in Self test mode 4 Connected protection unit not recognised 5 Incorrect communication speed set dip switch Baud 1 Check connections 2 FN 3 FN 4 Remove Vaux from PR010 K unit and from the protection unit then re power the two units simultaneously 5 Set the correct value 6 The LED Tx Int Bus is off 1 Wiring error 2 Anomalous situation 3 ...

Reviews: