This menu is activated with the
Ekip CI
module and an auxiliary power supply and local bus
enabled.
The
Self-test
command is available in the menu, and its selection activates a test of the LEDs
and output contact O61 in sequence:
1. Reset LED and contact closure of O61 (if open)
2. Turn on all the LEDs in sequence and then switch them off again
3. Opening of the O61 contact, lighting of the O61 led and subsequent reset
4. Restore initial conditions.
IMPORTANT: the self-test sequence involves sending the command to open the
output contact: verification of correct opening is the responsibility of the user.
Ekip Signalling
2K
This menu is activated with the
Ekip Signalling 2K
module and an auxiliary power supply and
local bus enabled.
NOTE: a menu is available for each
Ekip Signaling 2K module
, up to a maximum of
three
Within each submenu there is a
Self-test
command that activates the automatic sequence of
output tests (contacts and LEDs) and input test (LED), and includes the following operations:
1. Reset output contacts (= open) and LEDs (= off).
2. Turn on all the LEDs in sequence (output and input)
3. Closure and shutdown of the two output contacts in sequence, switching on the relative
LEDs.
4. Restore initial conditions
IMPORTANT: the Self-test command closes the contacts regardless of the
configuration set by the user: the safety of the devices connected to the Ekip
Signalling 2K modules, the verification of the correct closing of the contacts and
the lighting of the LEDs is the responsibility of the user
Zone selectivity
The menu has one or two sections that are visible depending on the available and enabled
protections:
Submenu
Reference selectivity
Inputs/Outputs managed
S Selectivity
S, S2, D (Forward)
SZi (DFi), SZo (DFo)
G Selectivity
G, D (Backward)
GZi (DBi), GZo (DBo)
In each submenu there are three fields useful for checking selectivity inputs and outputs:
Field
Description
Input
Provides the status of the selectivity input (On/Off)
Force Output
The selectivity output is activated
Release Output
The selectivity output is deactivated
To check the selectivity contacts refer to the commissioning procedure (page 14).
Summary of Contents for SACE Tmax XT2
Page 84: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 84 L curve Ekip M Touch S curve t k I2 ...
Page 86: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 86 G curve t k I2 G curve t k ...
Page 87: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 87 IU curve UV curve UV2 curve ...
Page 88: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 88 OV curve OV2 curve VU curve ...
Page 89: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 89 S V curve S2 V curve RV curve ...
Page 90: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 90 UF curve UF2 curve OF curve OF2 curve ...
Page 91: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 91 RP curve D curve ...
Page 92: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 92 OQ curve OP curve ...
Page 93: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 93 UP curve RQ curve ...
Page 94: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 94 ROCOF curve R JAM curve R STALL ...
Page 95: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 95 UC curve ...