1SDH002031A1002 ECN000092998 Rev. B
SACE Tmax XT2
– XT4 | 143
Remote
configurations
From the service connector (via Ekip Connect) or with communication by system bus it is possible
to access additional parameters
Parameter
Description
Default
Client/Server
Parameter for changing the configuration of the module from
Server Only to Client and Server and integrating the module into
an interactive data exchange network (see
Ekip Com Hub
on
IMPORTANT: if Client/Server, the module enables
the data to be exchanged as a normal Server
function
Server
only
Enable IEEE 1558
Permits the IEEE 1588 protocol for distributing the clock and
synchronization signal to be enabled
(1)
OFF
IEEE 1588 Master
Enables the module to be set as a master in the network segment
to which it belongs (synchronization clock)
OFF
IEEE 1588 Delay
mechanism
Enables the data exchange mode between module and master,
between Peer-to-Peer and End-to-End to be chosen
End-to-
End
Enable SNTP client
Permits enabling of SNTP distribution protocol of the clock and
synchronization signal
(1)
OFF
SNTP Server Address
Enables the network server to be set that supplies SNTP
0.0.0.0
Time zone
Defines the time zone to be used for synchronism
+00:00
Daylight Saving Time
Enables it to be selected whether there is daylight saving
time(ON) or not (OFF) in the country to which the synchronization
time refers.
OFF
Disable Gratuitos ARP
Permits (Enabled ARP) the periodic generation of a Gratuituos
ARP message to be enabled that is used by Ekip Connect to find
rapidly the modules with Ethernet scanning without its IP address
being known beforehand
ARP
enabled
Access protected by
password
Enables the writing operations conducted by the network to be
protected by a password (password request)
Standard
mode
TCP Modbus
password
With
access protected by enabled
password, this is the password
to use before each writing session
(2)
Local
access
NOTES:
(1)
Enable IEEE 1558 and Enable SNTP client
must not be enabled simultaneously
(2) the parameter can be modified only by system bus in remote configuration
Remote
information
From the service connector (via Ekip Connect) or with a system bus communication, additional
information can be accessed:
Information
Description
HW and Boot version
general module information
Flash CRC status and result
information on the correctness of the SW in the module
Ekip Link status
Signals connection errors of the Ethernet cable
SNTP Server Error
Communication error with the SNTP server
SNTP Server Synchronisation
Synchronism status with SNTP server
IEEE 1558 status
Valid with IEEE 1588 Master = ON, communicates the presence
(Slave or PTP Master Active) or absence (PTP Master but
Passive) of a higher level master
Summary of Contents for SACE Tmax XT2
Page 84: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 84 L curve Ekip M Touch S curve t k I2 ...
Page 86: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 86 G curve t k I2 G curve t k ...
Page 87: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 87 IU curve UV curve UV2 curve ...
Page 88: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 88 OV curve OV2 curve VU curve ...
Page 89: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 89 S V curve S2 V curve RV curve ...
Page 90: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 90 UF curve UF2 curve OF curve OF2 curve ...
Page 91: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 91 RP curve D curve ...
Page 92: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 92 OQ curve OP curve ...
Page 93: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 93 UP curve RQ curve ...
Page 94: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 94 ROCOF curve R JAM curve R STALL ...
Page 95: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 95 UC curve ...