1SDH002031A1002 ECN000092998 Rev. B
SACE Tmax XT2
– XT4 | 184
Features
Ekip Com Modbus TCP
integrates the following features:
Integrated status contacts (Open / Closed and Trip)
Backup battery to maintain the Date / Time in the event of absence of auxiliary alimetry
NOTA: refer to document 1SDH001000R0509 to replace the backup battery
Connections
Consult the electrical diagrams for 1SDM000068R0001 to connect the module to its
communication network and for terminal references.
The module is supplied with a 1mt long RJ45 cable to interface with your network.
See the instruction sheets 1SDH002009A1502 to connect the module to Ekip Touch.
Supply
Ekip Com Modbus TCP
is supplied directly by the Ekip Touch to which it is connected.
NOTE: in the absence of an auxiliary supply, the communication between Ekip Touch
and module is interrupted
Modes
Two operating modes are available, which can be configured from the menu:
Modes
Description
TCP
Modbus
Information and commands managed by single requests/questions, according to
mapping and rules of TCP Modbus protocol (see System Interface)
Server
HTTP
Information and commands available on a web page, which can be accessed by
a browser by inserting the IP Address of the module as the address.
The page has a login window requesting the user password to be entered that is
the same as the password required on the display to modify parameters.
Configurations
on menu
Activating the local bus is required to start communication between the module and Ekip Touch
and is available in the
Settings menu
(page 114).
If the module is detected correctly by Ekip Touch in the
Modules Settings
menu, the following
communication parameters can be configured:
Parameter
Description
Default
Function
Defines the mode between TCP Modbus and Server
HTTP
TCP Modbus
Static IP address
ON
Defines whether the module has a dynamic IP (Off)
address or static (On) IP address
If = On all the associated parameters are enabled
Off
Static IP address
Enables static IP to be selected
0.0.0.0
Static Network Mask
Enables the subnet mask to be selected
0.0.0.0
Static Gateway
address
Enables, in the presence of several subnets the IP
address of the node to which the module is connected
to be selected
0.0.0.0
Summary of Contents for SACE Tmax XT2
Page 84: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 84 L curve Ekip M Touch S curve t k I2 ...
Page 86: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 86 G curve t k I2 G curve t k ...
Page 87: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 87 IU curve UV curve UV2 curve ...
Page 88: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 88 OV curve OV2 curve VU curve ...
Page 89: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 89 S V curve S2 V curve RV curve ...
Page 90: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 90 UF curve UF2 curve OF curve OF2 curve ...
Page 91: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 91 RP curve D curve ...
Page 92: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 92 OQ curve OP curve ...
Page 93: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 93 UP curve RQ curve ...
Page 94: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 94 ROCOF curve R JAM curve R STALL ...
Page 95: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 95 UC curve ...