1SDH002031A1002 ECN000092998 Rev. B
SACE Tmax XT2
– XT4 | 201
Supply
Ekip Com Hub is powered directly by the
Ekip Touch
it is connected to.
NOTE: without an auxiliary power supply communication between Ekip Touch and the
module is interrupted
Menu
configurations
The activation of the local bus
– essential to start the communication between the module and
Ekip Touch
– is available in the
Settings
menu (page 29).
If the module is correctly detected by Ekip Touch, it is possible to configure the following
communication parameters in the
Settings-Modules
menu:
Parameter
Description
Default
Enable
Switches on/off the communication between module
and server
Static IP address
ON
Defines if the module has a dynamic IP address (
Off
)
or static (
On
)
If =
On
all the related parameters are enabled
Off
Static IP address
Enter the static IP address
0.0.0.0
Static Network
Mask
Enter the subnet mask
0.0.0.0
Static gateway
address
With multiple subnets, select
the IP address of the node to which the module is
connected
0.0.0.0
SNTP client
enable
Enable the SNTP protocol for clock signal distribution
and synchronization
OFF
SNTP Address.
Server
Identify the network server that provides SNTP
0.0.0.0
Password
Code needed to register the module in the Cloud
---
Remote firmware
update
Activation of the module's firmware update. There are
two parameters:
Enable
, to configure the firmware's download
Automatic
, to automate the module's update
OFF
Automatic
Menu
information
If the module is correctly detected by Ekip Touch, the following information is available in the
Information-Modules
menu:
Information
Description
SN and version
Module identifier and SW version
IP address
Module address, assigned to the module by a DHCP server when
connecting to the network with a dynamic IP, or settable from the menu
when using a static IP
NOTE: without a DHCP server, the module automatically
adopts a random IP address in the range 169.254.xxx.xxx
Network Mask
Identifies the method for recognizing the subnet to which modules
belong, with the possibility of searching for modules within a set of
defined recipients
Gateway address
IP address of the node to which the module is connected when there are
multiple subnets
MAC address
Address assigned by ABB with OUI (Organizationally Unique Identifier)
equal to ac:d3:64 that uniquely identifies the manufacturer of an
Ethernet device
Summary of Contents for SACE Tmax XT2
Page 84: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 84 L curve Ekip M Touch S curve t k I2 ...
Page 86: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 86 G curve t k I2 G curve t k ...
Page 87: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 87 IU curve UV curve UV2 curve ...
Page 88: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 88 OV curve OV2 curve VU curve ...
Page 89: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 89 S V curve S2 V curve RV curve ...
Page 90: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 90 UF curve UF2 curve OF curve OF2 curve ...
Page 91: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 91 RP curve D curve ...
Page 92: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 92 OQ curve OP curve ...
Page 93: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 93 UP curve RQ curve ...
Page 94: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 94 ROCOF curve R JAM curve R STALL ...
Page 95: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 95 UC curve ...