1SDH002031A1002 ECN000092998 Rev. B
SACE Tmax XT2
– XT4 | 161
48 - Ekip Com Hub
Ekip Com Hub
è a communication accessory that enables the data and measurements of Ekip
Touch and other devices to be gathered that are connected to the same plant and then be made
available on the server through an Ethernet network.
The configuration of the module is available via Ekip Connect or with the System Interface
document (page 114) in which all the details are listed.
The following ports are used by the module:
Port
Service
Notes
67/udp 68/udp
DHCP client
DHCP client enables alternatively to
static address = On
443/tcp
HTTPS
always active with enabled module
123/udp
SNTP
active with SNTP client enabled
53/udp
DNS
always active
The Ekip Com Modbus RTU and Ekip Com TCP Modbus modules can be configured to support
Ekip Com Hub
in gathering data to be sent to Cloud. See Getting Started 1SDC200063B0201.
To connect
Ekip Com Hub
to Ekip Touch, the
Ekip Cartridge
(page 129) and
Ekip Supply
(page
130) accessories are required.
Safety
The module uses the HTTPS protocol and can be connected to the Internet.
IMPORTANT: it is customer's sole responsibility to provide and continuously
ensure a secure connection between the module and customer network or any
other network (as the case may be); customer shall establish and maintain any
appropriate measures (such as but not limited to the installation of firewalls,
application of authentication measures, encryption of data, installation of anti-
virus programs, etc) to protect the product, the network, its system and the
interface against any kind of security breaches, unauthorized access,
interference, intrusion, leakage and/or theft of data or information.
ABB Ltd and its affiliates are not liable for damages and/or losses related to such
security breaches,any unauthorized access, interference, intrusion, leakage
and/or theft of data or information.
Connections
Consult
the electrical diagrams for 1SDM000068R0001 to connect the module to its communication
network and for the terminals references.
For the communication bus, a Cat.6 S/FTP cable must be used (Cat.6 with double S/FTP
shield).
the instruction sheets 1SDH002009A1503 to connect the module to
Ekip Supply
and Ekip
Touch.
Supply
Ekip Com Hub is supplied directly by the
Ekip Supply module
to which it is connected.
NOTE: in the absence of an auxiliary supply, the communication between Ekip Touch
and module is interrupted
Summary of Contents for SACE Tmax XT2
Page 84: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 84 L curve Ekip M Touch S curve t k I2 ...
Page 86: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 86 G curve t k I2 G curve t k ...
Page 87: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 87 IU curve UV curve UV2 curve ...
Page 88: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 88 OV curve OV2 curve VU curve ...
Page 89: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 89 S V curve S2 V curve RV curve ...
Page 90: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 90 UF curve UF2 curve OF curve OF2 curve ...
Page 91: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 91 RP curve D curve ...
Page 92: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 92 OQ curve OP curve ...
Page 93: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 93 UP curve RQ curve ...
Page 94: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 94 ROCOF curve R JAM curve R STALL ...
Page 95: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 95 UC curve ...