1SDH002031A1002 ECN000092998 Rev. B
SACE Tmax XT2
– XT4 | 165
49 - Ekip Signalling 2K
Ekip Signalling 2K
is an external accessory signalling module that enables programmable
inputs/outputs to be managed.
The module has:
two contacts for output signals and relative status LED
two digital inputs and relative status LED
a power LED with the startup status of the module
To connect
Ekip Signalling 2K
to Ekip Touch, the
Ekip Cartridge
(page 129) and
Ekip Supply
(page 130) accessories are required.
Models
Ekip Touch can be configured with three different Signalling 2K modules:
Ekip Signalling 2K-1
,
Ekip Signalling 2K-2
and
Ekip Signalling 2K-3
.
The three modules are identical in terms of characteristics and installation methods, except for:
display menus on unit, cablings and addresses for external communication, that are specific for
each model.
NOTE: if not specified, the information in the following chapter applies to all models
All the modules can be connected simultaneously to Ekip Touch to increase the potential of unit
(for example: to increase number of input and output).
IMPORTANT: in each Ekip Touch can be installed only one module per type; it is
not admitted the connection of two or three equal modules (for example: two Ekip
Signalling 2K-3)
Connections
Consult
the electrical diagrams for 1SDM000068R0001 for terminal references; for external
cabling, AWG 22-16 cables with a maximum external diameter of 1.4 mm must be used
the instruction sheets 1SDH002009A1503 to connect the module to
Ekip Supply
and
Ekip Touch.
Supply
Ekip Com Signalling 2K
is supplied directly by the Ekip Supply module to which it is connected .
NOTE: in the absence of an auxiliary supply, the communication between Ekip Touch
and module is interrupted
Input
Ekip Touch can be configured in such a way that the status of the inputs corresponds to actions
or signals, with different programming options (see
Menu
on page 166)
The connection or each input (H11 and H12 for model 2K-1, H21 and H22 for model 2K-2, H31
and H32 for model 2K-3) must be carried out in reference with the common contacts (HC).
The module permits two logic statuses, interpreted by Ekip Touch according to the configuration
selected for each contact:
Status
Electrical condition
Configuration of contact
Status detected by Ekip
Touch
Open
Circuit open
Active open
ON
Active closed
OFF
Closed
Short circuit
Active open
OFF
active closed
ON
Summary of Contents for SACE Tmax XT2
Page 84: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 84 L curve Ekip M Touch S curve t k I2 ...
Page 86: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 86 G curve t k I2 G curve t k ...
Page 87: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 87 IU curve UV curve UV2 curve ...
Page 88: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 88 OV curve OV2 curve VU curve ...
Page 89: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 89 S V curve S2 V curve RV curve ...
Page 90: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 90 UF curve UF2 curve OF curve OF2 curve ...
Page 91: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 91 RP curve D curve ...
Page 92: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 92 OQ curve OP curve ...
Page 93: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 93 UP curve RQ curve ...
Page 94: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 94 ROCOF curve R JAM curve R STALL ...
Page 95: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 95 UC curve ...