1SDH002031A1002 ECN000092998 Rev. B
SACE Tmax XT2
– XT4 | 183
54 - Ekip Com Modbus TCP
Ekip Com Modbus TCP
is a communication accessory that enables Ekip Touch to be integrated
into an Ethernet network with Modbus TCP communication protocol, with remote supervision and
control functions, in two different modes, standard and HTTP server.
The module is configured as master and from remote it is possible to
read Ekip Touch information and measurements
manage certain commands, including opening and closing actuator (MOE-E)
access information and parameters that are not available on the display
NOTE: the remote open and close commands to the switch can be run only if Ekip
Touch is in Remote configuration
To map the module in its communication network, the document System Interface is available
(page 128) that lists the necessary communication and command details.
Depending on the parameters set, which are illustrated on subsequent pages, the following
module ports are used:
Port
Service
Notes
502/tcp
TCP Modbus
Valid for TCP Modbus modes
80/tcp
Server HTTP
Valid for Server HTTP modes
319/udp
IEEE 1588
Valid with IEEE 1588 protocol enabled
320/udp
68/udp
DHCP client
DHCP client enables alternatively to:
static address
=
On
IMPORTANT: each XT2 / XT4 circuit breaker can accommodate only one module;
configuration with external communication modules is not permitted if an internal
module is present
Safety
As the module enables the actuator to be controlled that is connected to Ekip Touch and enables
unit data to be accessed, it can be connected only to networks meeting all the necessary security
and unauthorized-access prevention requirements (e.g. the control system network of a plant).
IMPORTANT:
It is customer's sole responsibility to provide and continuously ensure a
secure connection between the module and customer network or any other
network (as the case may be); customer shall establish and maintain any
appropriate measures (such as but not limited to the installation of firewalls,
application of authentication measures, encryption of data, installation of
anti-virus programs, etc) to protect the product, the network, its system and
the interface against any kind of security breaches, unauthorized access,
interference, intrusion, leakage and/or theft of data or information.
ABB Ltd and its affiliates are not liable for damages and/or losses related to
such security breaches,any unauthorized access, interference, intrusion,
leakage and/or theft of data or information.
The module cannot be connected directly to the Internet; connect only to
dedicated Ethernet networks, with Modbus TCP communication protocol
Summary of Contents for SACE Tmax XT2
Page 84: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 84 L curve Ekip M Touch S curve t k I2 ...
Page 86: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 86 G curve t k I2 G curve t k ...
Page 87: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 87 IU curve UV curve UV2 curve ...
Page 88: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 88 OV curve OV2 curve VU curve ...
Page 89: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 89 S V curve S2 V curve RV curve ...
Page 90: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 90 UF curve UF2 curve OF curve OF2 curve ...
Page 91: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 91 RP curve D curve ...
Page 92: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 92 OQ curve OP curve ...
Page 93: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 93 UP curve RQ curve ...
Page 94: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 94 ROCOF curve R JAM curve R STALL ...
Page 95: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 95 UC curve ...