ABB | SACE Tmax XT
114 | © 2019 ABB | 1SDH002039A1002 - ECN000093027 - Rev. A
Settings | 1 - Main settings
Settings
1 - Main settings
Foreword
All the following parameters are available either directly, or from the
Settings
menu, in the conditions
established by Ekip Touch on the basis of the version and configuration described.
To correctly address parameters which are present in the menu but not described below:
• Circuit-breaker: Hardware Trip, T Protection, Neutral Protection
• Phase sequence
• Monitor time
• Power Controller
• Load Shedding
• Network Analyzer
• Datalogger
• Dual Set
• Functions
please consult the
Settings
menu overview (page 33).
WARNING! changes to the settings must be made in the absence of protection alarms
Configuration
The
Circuit breaker-Configuration
menu, allowing the presence of the
External neutral
sensor to be activated,
is available for the 3P CB (page 200).
Activation of the configuration with
External neutral
(3P + N) enables:
• histograms of phase Ne in the
Histograms
page
• neutral current measurements
• submenu for configuring the Neutral protection (
Neutral Protection
)
• neutral current recording in the case of TRIP
With 3P CB, the parameter is set by default as: 3P.
Line frequency
Frequency adjustment is performed to set the installation frequency; the choice is between 50 Hz and 60 Hz.
NOTE:
the measurements are taken on the basis of the set grid frequency: incorrect configuration
of the parameter may lead to abnormal measurements and protection
Ekip Touch is supplied with the parameter setting that suits the ordered configuration.