ABB | SACE Tmax XT
External accessories | 9 - Ekip Com EtherNet/IP TM
147 | © 2019 ABB | 1SDH002039A1002 - ECN000093027 - Rev. A
Connections
For references about the connection and terminals, please consult document
; a cable
of the Class 6 S/FTP type (Class 6 with double screening S/FTP) must be used for the communication bus.
To connect the module to
Ekip Supply
and
Ekip Cartridge
, please consult document
Power supply
Ekip Com EtherNet/IP
TM
is supplied directly by the
Ekip Supply
module to which it is connected.
NOTE:
communication between Ekip Touch and the module is interrupted in the absence of
auxiliary power supply
Interface
the module has three signaling leds:
1
2
Figure 48
LEDs
Description
Power
Signals the on status and correct communication with Ekip Touch:
• off: module off
• on steady or flashing synchronized with the Power led of Ekip Touch: module on
and communication with Trip unit present.
• flashing not synchronized with the Power led of Ekip Touch (2 fast flashes per
second): module on and communication with Trip unit absent.
Link (
1
)
Indicates the communication state:
• off: incorrect connection, signal absent.
• on steady: connection correct
Activity (
2
)
Indicates the communication state:
• off: no activity on line
• flashing: activity on line present (receiving and/or transmitting)
Configurations via menu
Local bus activation, which is essential for starting the communication between module and Ekip Touch, is
available in the
Settings
menu (page 33).
The following communication parameters can be configured if the module has been correctly detected by
Ekip Touch in the
Settings
-
Modules
menu:
Parameter
Description
Default
Static IP address ON
Defines whether the IP address of the module is dynamic
(Off) or static (On); If = On, all the associated parameters are
enabled
OFF
Static address IP address
Enables the static IP to be selected
0.0.0.0
Static Network Mask
Enables the subnet mask to be selected
0.0.0.0
Static Gateway address
When there are several subnets, enables the IP address of
the node to which the module is connected to be selected
0.0.0.0