ABB | SACE Tmax XT
External accessories | 13 - Ekip Signalling 2K
163 | © 2019 ABB | 1SDH002039A1002 - ECN000093027 - Rev. A
Output parameters
All the available inputs enable the following parameters to be configured:
Parameter
Description
Default
Signal source
Event which activates the output and switches the contacts.
Different protection proposals, statuses and thresholds are
available on the display; the Custom mode can be configured via
Ekip Connect so as to extend the solutions and combine several
events
None
Delay
Minimum duration of the presence of the source before the output
is activated; the delay is given in seconds and can be set within
range: 0 s to 100 s, in 0.01 s steps
NOTES
:
• the output will not be switched if the source is deactivated
before this time has elapsed
• if delay = 0 s the source must still be present for longer
than 300 µS
0 s
Contact Type
Defines the rest status of the contact with source not present
between: open (NO) and closed (NC)
NO
Latched
(1)
Allows the output (and relative status led) to be kept activated
(On) or deactivated (Off) when the event disappears
OFF
min Activation Time
(2)
Defines the minimum closing time of the contact following the
rapid presence of sources:
• Source duration < min. activation = contact is activated for the
minimum activation time
• Source duration
≥
min. activation = contact is activated for as
long as the source persists
Choose between: 0 ms, 100 ms, 200 ms
0 ms
(1)
deactivate the latchings of the outputs used if Ekip Measuring is used for the Power Controller function
(2)
if Ekip Measuring is used for the Power Controller function, the Power Controller option will also be available;
if selected, the output is kept activated for a set time that depends on the function, regardless of whether the
event that activated it persists
About
The specific menu of the module available in the
About
-
Modules
menu contains:
• the serial number and version of the module
• the statuses of the inputs (On/Off) and outputs (Open/Closed)
Test
The test area in the
Test
menu is activated if the
Ekip Signalling 2K
module is detected correctly.
For details of the test characteristics, please consult page 121.
Remote information
Certain additional information concerning the version and status of the module is available via the service
connector (via Ekip Connect) or by communication via system bus; the information includes: HW and Boot
version, CRC status (correctness of the SW in the module).