ABB | SACE Tmax XT
174 | © 2019 ABB | 1SDH002039A1002 - ECN000093027 - Rev. A
External accessories | 16 - Ekip CI
Configuration
The module parameters can be configured in the
Settings
-
Modules
-
Ekip CI
menu:
Parameter
Description
Default
Enable
Activates/deactivates certain functions and their availability in the
parameters menu:
• if On: all the inputs, outputs and relative functions are activated
• if Off: only input I61 is activated: the command function of O61 is
off
Off
Polarity
Defines whether input I63 is interpreted as On by Ekip Touch when it
is open (
Active open
) or when it is closed (
Active Closed
)
Active closed
Delay
Minimum activation time of input I63 before the re-opening command
of contact O61 is sent; the delay is given in seconds and can be set
within range: 0 s to 100 s, in 0.01 s steps
NOTES
:
• if the input is deactivated before this time has elapsed, the re-
opening command is not sent
• if delay = 0 s the input must still be present for longer than
300 µS
0.1 s
Measurements
The specific area of the module, containing the temperature measurement of probe PT100 if connected and
activated, will be available in the
Measurements
menu if
Ekip CI
is correctly detected by Ekip Touch.
NOTE:
value “- - -” will be displayed if no probe is detected
Test
The test area in the
Test
menu is activated if the
Ekip CI
module is detected correctly.
For details of the test characteristics, please consult page 34.
About
If
Ekip CI
is detected correctly by Ekip Touch, the specific area of the module will be available in the
About
-
Modules
menu, containing:
• the serial number and version of the module
• activation status of the input for temperature probe PT100
Remote information
Certain additional information concerning the version and status of the module is available via the service
connector (via Ekip Connect) or by communication via system bus; the information includes: HW and Boot
version, CRC status (correctness of the SW in the module).